Plan Review Notes
Plan Review Notes For Permit 03091789
Permit Number 03091789
Review Stop B
Sequence Number 1
Notes
Date Text
2003-10-27 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECIEPT FOR
 THE COUNTY IMPACT FEES.
  
 2) A CORRECTED SURVEY WITH SET BACKS
 APPROVED BY ZONING IS REQUIRED BEFORE A
 PERMIT WILL BE ISSUED.
  
 3) SPECIFY THE SIZE OF THE BATHROOM DOOR
 ON THE FLOOR PLAN.
  
 4) SPECIFY THE SIZE OF THE GLASS BLOCK
 OPENING AT THE MASTER BATHROOM.
  
 5) PROVIDE A DETAIL OF THE STEP DOWN
 SLAB FOUNDATION AT THE GARAGE. INDICATE
 THE LOCATION AND SIZE OF THESTEEL
 REINFORCEMENT.
  
 6) ON SHEET 4 THERE ARE NO VERTICAL
 REINFORCED FILLED CELLS SHOWN AT THE
 MASTER BEDROOM WINDOW, DOOR, NOOK WINDOW
 AND AT THE CORNERS IN THIS AREA. PLEASE
 CORRECT.
  
 7) IDENTIFY THE LINTELS AT THE ENTRY
 PORCH ON SHEET A4.
  
 8) SUBMIT TECHNICAL BULLETIN FROM USP
 FOR INVERTED INSTALLATION OF SHA 424
 CONNECTOR.
  
 9) FBC 1609 DOES NOT ALLOW A ONE-THIRD
 INCREASE IN THE STEEL CALCULATIONS FOR
 LOAD COMBINATIONS. PLEASE REVISE THE
 UPLIFT VALUE FOR THE HETA 20 ON SHEET 5
 TO 1240#(SEE SIMPSON HIGH WIND-RESISTANT
 CATALOG) AND ADJUST THE VALUES OF THE
 COMBINED CONNECTORS USING THIS STRAP.
  
 10) THE UPLIFT VALUE FOR THE RT24
 CONNECTOR SPECIFIED FOR THE 4X4 POST IS
 1125#. THE VALUE FOR TWO IS 2250#, NOT
 2600#. PLEASE REVISE.
  
 11) SPECIFY THE FASTENERS, ANCHOR BOLT
 SIZE AND EMBEDMENT AND MANUFACTURER FOR
 THE MTT 28B CONNECTOR AT THE 4X4 POST ON
 SHEET 5.
  
 12) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED AND DATED BY THE OWNER/
 AGENT PER FBC CHAPTER 13.
  
 13) THE ADDENDUM TO THE SOIL REPORT
 LETTER FROM ALLTERRA IS REQUIRED TO BE
 SEALED BY THE ENGINEER.
  
 14) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS.
  
 15) REVISE THE GARAGE DOOR BUCK FASTER
 SPACING ON SHEET D1 TO CONCUR WITH THE
 PRODUCT APPROVAL FOR THE CLOPAY GARAGE
 DOOR.
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
 - GLAZED OUTSWING FRENCH DOORS
 - FIXED GLASS EYEBROW WINDOW
 - STRUCTURAL MULLIONS
 - SLIDING GLASS DOORS
 - DOUBLE OUTSWING OPAQUE DOORS AT ENTRY
  
 17) THE GLASS BLOCK AT THE MASTER BATH
 IS IN A HAZARDOUS LOCATION AND IS
 REQUIRED TO HAVE A MINIMUM UNIFORM FACE
 THICKNESS OF 0.25" PER FBC 2405.2.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714