| 2003-09-29 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATIONMAKE NECESSARY CHANGES TO | | | PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110.9. | | | | | | 2} PLEASE DRAW A RISER DIAGRAM SHOWING | | | CONDUCTOR AND CONDUIT SIZES PER 215.5. | | | | | | 3} SHOW GROUNDING EELCTRODE SYSTEM PER | | | 250.52. | | | | | | 3} THE GROUND ROD MUST BE A MINIMUM OF | | | 8' PER 250.52(A)(5). | | | | | | 4} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE A MINIMUM OF #4 PER 250.66. | | | | | | 5} INDICATE ON THE RISER WHETHER THE | | | SERVICE IS OVERHEAD OR UNDERGROUND. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH. | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|