Plan Review Notes
Plan Review Notes For Permit 03091739
Permit Number 03091739
Review Stop E
Sequence Number 1
Notes
Date Text
2003-09-29 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONMAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 2} PLEASE DRAW A RISER DIAGRAM SHOWING
 CONDUCTOR AND CONDUIT SIZES PER 215.5.
  
 3} SHOW GROUNDING EELCTRODE SYSTEM PER
 250.52.
  
 3} THE GROUND ROD MUST BE A MINIMUM OF
 8' PER 250.52(A)(5).
  
 4} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE A MINIMUM OF #4 PER 250.66.
  
 5} INDICATE ON THE RISER WHETHER THE
 SERVICE IS OVERHEAD OR UNDERGROUND.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH.
 ELECTRICAL PLAN REVIEW
 561/805-6718