2004-05-14 00:00:00PROVISO:
 PLEASE NOTE, LETTER STATES DUCT SMOKE
 DETECTOR TO BE LOCATED IN THE RETURN AIR
 DUCT. PER 2001 FBC(M) 606.2.1 & NFPA 90A
 6.4.2.1, THE DUCT SMOKE DETECTOR SHALL
 BE INSTALLED IN THE SUPPLY AIR SYSTEM.
  
 CURB INSTALLATION SHALL COMPLY WITH 2001
 FBC 1511.7 SEE ATTACHED.
  