| 2004-05-14 00:00:00 | PROVISO: | | | PLEASE NOTE, LETTER STATES DUCT SMOKE | | | DETECTOR TO BE LOCATED IN THE RETURN AIR | | | DUCT. PER 2001 FBC(M) 606.2.1 & NFPA 90A | | | 6.4.2.1, THE DUCT SMOKE DETECTOR SHALL | | | BE INSTALLED IN THE SUPPLY AIR SYSTEM. | | | | | | CURB INSTALLATION SHALL COMPLY WITH 2001 | | | FBC 1511.7 SEE ATTACHED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|