2003-12-12 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING. BUILDING ADDRESS
 IS REQUIRED TO BE MOUNTED ON BUILDING
 AT LEAST 6" HIGH.
  
 2) EXIT SIGNS STILL SHOWN DIRECTING
 PERSONS TO EXIT INTO THE WAREHOUSE.
 NO EXIT SIGNS DIRECTING PERSONS INTO
 AND OUT OF THE LUNCH ROOM AS
 PREVIOUSLY AGREED UPON.
  
 3) SITE DEVELOPMENT PLANS ONLY
 DISPLAYS ONE FIRE HYDRANT. PLEASE
 DISPLAY OTHER FIRE HYDRANTS LOCATED
 IN THE GENERAL VICINITY.
  
 4) HOW DOES FIRE AND PARAMEDICAL
 EQUIPMENT GAIN ACCESS THRU THE SLIDING
 GATE. IF GATE IS ELECTRIC, WHAT
 HAPPENS WHEN LOSS OF POWER OCCURS.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6) NO FIRE EXTINGUISHERS SHOWN IN
 WAREHOUSE AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910