| Date |
Text |
| 2003-10-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1) SUBMIT CALCULATIONS FOR ROOF GUTTERS | | | AND DOWNSPOUTS PER TABLE 1106.6 SHOW SQ. | | | FT. OF ROOF, & SHOW 1/2 AREA OF ALL | | | VERTICAL WALLS INCLUDING PARAPETS IN THE | | | CALCULATIONS. INDICATE SLOPE OF GUTTER, | | | AND SHOW SLOPE OF GUTTER ON PLANS. | | | 2) PLEASE SUBMIT 2 COMPLETE SETS OF | | | PLANS. PLANS WERE SUBMITTED AS SEPARATE | | | ROLLS. 104.2.1-104.2.1.3 | | | 3) A DRINKING FOUNTAIN AND A SERVICE | | | SINK ARE REQUIRED PER TABLE 403.1. | | | 4) SHT P-2 CLEANOUT REQUIRED PER SECTION | | | 708.3.1 ON BLDG DRAIN BETWEEN ROOMS 003 | | | AND 012. SHOW ON FLOOR PLAN AND RISER | | | DIAGRAM. | | | 5) INDICATE TYPE AND AMOUNT OF MATERIAL | | | BEING STORED IN WAREHOUSE. NEW COMMENTS | | | MAY ARISE ACCORDING TO RESPONSE OF THIS | | | COMMENT. | | | 6) TOILET ROOMS SHALL COMPLY WITH SECT- | | | IONS 11-4.16, 11-4.19, AND 11-4.22 WITH | | | ALL SUBSECTIONS. SUBMIT DETAILS. | | | 7) LUNCH ROOM SINK SHALL COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | PROVIDE DETAILS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|