2003-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) SUBMIT CALCULATIONS FOR ROOF GUTTERS
 AND DOWNSPOUTS PER TABLE 1106.6 SHOW SQ.
 FT. OF ROOF, & SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN THE
 CALCULATIONS. INDICATE SLOPE OF GUTTER,
 AND SHOW SLOPE OF GUTTER ON PLANS.
 2) PLEASE SUBMIT 2 COMPLETE SETS OF
 PLANS. PLANS WERE SUBMITTED AS SEPARATE
 ROLLS. 104.2.1-104.2.1.3
 3) A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED PER TABLE 403.1.
 4) SHT P-2 CLEANOUT REQUIRED PER SECTION
 708.3.1 ON BLDG DRAIN BETWEEN ROOMS 003
 AND 012. SHOW ON FLOOR PLAN AND RISER
 DIAGRAM.
 5) INDICATE TYPE AND AMOUNT OF MATERIAL
 BEING STORED IN WAREHOUSE. NEW COMMENTS
 MAY ARISE ACCORDING TO RESPONSE OF THIS
 COMMENT.
 6) TOILET ROOMS SHALL COMPLY WITH SECT-
 IONS 11-4.16, 11-4.19, AND 11-4.22 WITH
 ALL SUBSECTIONS. SUBMIT DETAILS.
 7) LUNCH ROOM SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 PROVIDE DETAILS.
  