| Plan Review Notes For Permit 03091729 |
| Permit Number |
03091729 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-27 00:00:00 | DENIED: | | | 1.PLEASE NOTE THE ADDENDUM TO PLANS | | | SHALL BE SIGNED, SEALED AND DATED BY THE | | | ENGNINEER AS PER F.S. 471.025 | | | | | | 2.ADDENDUM INDICATES A DOOR TRANSFER | | | GRILLE.PLANS REFLECT THE DOOR IS | | | LOCATED BETWEEN THE WAREHOUSE AND THE | | | OFFICE AREA, THIS HAS A TWO HOUR RATING. | | | TRANSFER GRILLE WILL REQUIRE A FIRE | | | DAMPER AS PER 2001 FBC(M) 607.1.2. | | | | | | 3.NO COMBUSTIBLES ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM (2001 FBC(M) | | | 602.2.1). | | | | | | 4.PLEASE INDICATE WHAT WILL BE STORED | | | IN THE WAREHOUSE AND THE STORAGE AREA. | | | | | | 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS PER NFPA 90A | | | 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|