Plan Review Notes
Plan Review Notes For Permit 03091729
Permit Number 03091729
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-10-17 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 2) PLEASE EXPLAIN EXITING RATIONALE.
 SOME EXIT SIGNS ARE DIRECTING PERSONS
 INTO THE WAREHOUSE. THE WAREHOUSE
 IS MORE HAZARDOUS THAN THE OFFICE
 AREA. ONLY ONE MEANS OF EGRESS IS
 SHOWN FROM THE OFFICE EXCEPT GOING
 BACK INTO THE WAREHOUSE.
  
 3) BUILDING ADDRESS IS REQUIRED.
  
 4) A KNOX-BOX WILL BE REQUIRED.
  
 5) WHAT WILL BE STORED IN THE WAREHOUSE.
  
 6) NO EMERGENCY LIGHTS OR EXIT SIGNS
 SHOWN IN MEZZANINE ELECTRICAL PLAN,
 PAGE E-2.
  
 7) NO MENTION OF ANY FIRE EXTINGUISHERS.
  
 8) PLEASE EXPLAIN SINGLE MEANS OF
 EGRESS FROM STORAGE AREA.
  
 9) NO COMBUSTIBLES ALLOWED IN THE
 RETURN AIR PLENUM.
  
 10) PLEASE DISPLAY ALL FIRE HYDRANTS
 IN THE VICINITY OF THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910