| Plan Review Notes For Permit 03091729 |
| Permit Number |
03091729 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-17 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED | | | PRIOR TO, DURING AND AFTER | | | CONSTRUCTION. | | | | | | 2) PLEASE EXPLAIN EXITING RATIONALE. | | | SOME EXIT SIGNS ARE DIRECTING PERSONS | | | INTO THE WAREHOUSE. THE WAREHOUSE | | | IS MORE HAZARDOUS THAN THE OFFICE | | | AREA. ONLY ONE MEANS OF EGRESS IS | | | SHOWN FROM THE OFFICE EXCEPT GOING | | | BACK INTO THE WAREHOUSE. | | | | | | 3) BUILDING ADDRESS IS REQUIRED. | | | | | | 4) A KNOX-BOX WILL BE REQUIRED. | | | | | | 5) WHAT WILL BE STORED IN THE WAREHOUSE. | | | | | | 6) NO EMERGENCY LIGHTS OR EXIT SIGNS | | | SHOWN IN MEZZANINE ELECTRICAL PLAN, | | | PAGE E-2. | | | | | | 7) NO MENTION OF ANY FIRE EXTINGUISHERS. | | | | | | 8) PLEASE EXPLAIN SINGLE MEANS OF | | | EGRESS FROM STORAGE AREA. | | | | | | 9) NO COMBUSTIBLES ALLOWED IN THE | | | RETURN AIR PLENUM. | | | | | | 10) PLEASE DISPLAY ALL FIRE HYDRANTS | | | IN THE VICINITY OF THE BUILDING. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|