Plan Review Notes
Plan Review Notes For Permit 03091729
Permit Number 03091729
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-15 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE CLARIFY USE OF WAREHOUSE/
 STORAGE AREA. ANY STORAGE THAT MEETS
 NEC ART 500 NEEDS TO BE NOTED AND MAPPED
 OUT.
  
 2)NOTE: PLEASE CLARIFY "SHOW" RM RECEPTS
 REQ'D PER 210.62.
  
 3)NOTE: PLEASE SEE THAT PANEL SCHEDULE
 APPEARS TO HAVE SIGN CIRCUIT REQ'D PER
 600.5, HOWEVER CAN NOT FIND THIS ON
 POWER OR LIGHTING PLAN? PLEASE LOCATE.
  
 4)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL EQUIPMENT, INCLUDING PANELS.
 IT IS NOTED MAIN IS A FUSED DISC.
 ALL MAINS/PANELS/BRKRS ARE TO BE RATED
 FOR THE AVAILABLE FUALT CURRENT.110.9/
 215.5
  
 5)NOTE: PLEASE CLARIFY POU WATER HEATERS
 , KW RATING SHOWN AT 4.5KW? THIS SEEMS
 TO BE HIGH FOR A POU WH?
  
 6)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS INCLUDING FOR ROOF TOP EQUIPMENT.
 PLEASE ALSO SHOW GFI RECEPT REQ'D FOR
 210.63.
  
 7)NOTE:PLEASE SEE THAT ENTRY LTAPPEAR TO
 BE SHOWN CIRCUITED TO PANEL "A", YET
 PANEL "M" SCHEDULE SHOWS LTS COMING FROM
 THERE? PLEASE CLARIFY.
  
  
 ***** PLEASE SEE THAT ALL PLANS WERE
 SUBMITTED IN INDIVIDUAL ROLLS? PLEASE
 DIVIDE ALL PLANS UP INTO TWO COMPLETE
 SETS FOR REVIEWING AND STAMPING.
 IF JOB IS DETERMINED TO BE A "THRESHOLD"
 JOB, THEN PLEASE MAKE THREE COMPLETE SET
 -S.*********
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]