Text |
| 2003-10-21 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT A PAID RECEIPT FOR THE IMPACT |
| | FEES. |
| | |
| | 3) SUBMIT A SUB-SURFACE SOIL REPORT |
| | INDICATING THE SAFE BEARING CAPACITY OF |
| | THE SOIL AS REQUIRED BY FBC 1804.2.2. |
| | |
| | 4) THE ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE SIGNED BY THE OWNER/AGENT. IN |
| | ORDER TO TAKE THE CEILING FAN CREDIT ON |
| | THE ENERGY CALCS, A MINIMUM OF ONE |
| | CEILING FAN IS REQUIRED IN ALL PRIMARY |
| | LIVING AREAS. THERE IS NO CEILNG FAN |
| | SPECIFIED IN THE LIVING ROOM. PLEASE |
| | INDICATE THE REQUIRED SIZES OF THE FANS |
| | ON THE PLANS. SEE FBC 13-607.2.A.3.1 AND |
| | TABLE 6-6. |
| | |
| | 5) SUBMIT A SIGNED AND SEALED SURVEY. |
| | |
| | 6) INDICATE ON THE PLANS THE SQFT |
| | BREAKDOWN OF THE STRUCTURE. (A/C AREA, |
| | GARAGE, COVERED PORCHES, ETC.) |
| | |
| | 7) THE GARAGE BUCK DETAIL 3B ON 4S4 |
| | REQUIRES A MINIMUM OF 8X16 BLOCK WITH |
| | TWO FILLED CELLS WITH ONE #5 ON EACH |
| | SIDE OF THE GARAGE OPENINGS. THE PLAN |
| | SPECIFIES ONE REINFORCED FILLED CELL ON |
| | EACH SIDE OF THE OPENINGS. PLEASE |
| | CORRECT. |
| | |
| | 8) THE FOUNDATION PLAN ON SHEET 4 |
| | SPECIFIES WIRE MESH IN THE SLAB AND |
| | DETAIL 1 ON 4S1 SPECIFIES FIBER MESH |
| | CONCRETE FOR THE SLAB. PLEASE CLARIFY. |
| | |
| | 9) THE SECTION AT THE GARAGE DOOR ON 4 |
| | IS MISLABELED. IT SHOULD BE LABELED 3 |
| | ON 4S1. |
| | |
| | 10) DETAIL 8 ON 4S1 FOR THE SECTION AT |
| | THE INTERIOR GARAGE WALL REFERENCED ON |
| | SHEET 4 HAS BEEN CROSSED OUT. PLEASE |
| | CORRECT. |
| | |
| | 11) PLEASE MAKE CORRECTIONS TO CONNECTOR |
| | CHART ON 5B. THE 775# UPLIFT VALUE IS |
| | FOR 10D NAILS. THE VALUE FOR 10D X 1-1/2 |
| | NAILS 735#. THE USP TAPR216 CONNECTOR IS |
| | NO LONGER LISTED IN THE CATALOG. SPECIFY |
| | A CURRENT CONNECTOR. THE LONGER HTT 22 |
| | STRAP WILL BE REQUIRED FOR THE (32) 10D |
| | NAILS FOR A 5370# UPLIFT. THE UPLIFT FOR |
| | THE NFM6X16 HAS BEEN REVISED TO 1325# IN |
| | THE 2003 USP CATALOG. PLEASE REVISE. |
| | SEE 2003 USP CATALOG. |
| | |
| | 12) PLEASE PROVIDE MANUFACTURER'S SPECS. |
| | AND LISTING INFORMATION FOR GAS COOK TOP |
| | ON COVERED PATIO. |
| | |
| | 13) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | INDICATING THE HORIZONTAL SLIDING |
| | WINDOW IN BEDROOM #4 MEETS THE EGRESS |
| | REQUIREMENTS OF FBC 1005.4. |
| | |
| | 14)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 15) INDICATE THE LOCATION AND SIZE OF |
| | THE ATTIC ACCESS REQUIRED BY FBC 2309.6. |
| | |
| | 16) SUBMIT THE ENGINEERED INSTALLATION |
| | DRAWINGS FOR THE STORM PANELS. SUBMIT A |
| | KEY PLAN THAT CORRESPONDS TO THE |
| | INSTALLATION SCHEDULE. THE NUMBERS AND |
| | SIZES ON THE SHUTTER SCHEDULE DOES NOT |
| | CORRESPOND WITH THE SHUTTER SCHEDULE ON |
| | 4S4. |
| | |
| | 17) SUBMIT SITE SPECIFIC ENGINEERING W/ |
| | DETAILED SHOP DRAWINGS, SPECIFICATIONS |
| | AND RATIONAL ANALYSIS AND/OR TEST DATA |
| | ASSURING SAFE PERFORMANCE FOR THE BUTT |
| | GLASS ASSEMBLY IN THE MORNING ROOM. THE |
| | PRODUCT APPROVAL FOR THE STORE FRONT |
| | THAT WAS SUBMITTED IS NOT FOR A BUTT |
| | GLASS ASSEMBLY. |
| | |
| | 18) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE HORIZONTAL SLIDING WINDOWS DOES NOT |
| | LIST A THREE PANEL WINDOW AS SHOWN FOR |
| | BEDROOM #4. SUBMIT APPROPRIATE PRODUCT |
| | APPROVAL. |
| | |
| | 19) THE REQUIRED WINDLOAD PRESSURES FOR |
| | THE 36SH WINDOWS IN THE MASTER BEDROOM |
| | EXCEED THE NEGATIVE PRESSURE OF -43.10 |
| | IN THE PRODUCT APPROVAL FOR 3/16" |
| | ANNEALED GLASS. SUBMIT APPROPRIATE |
| | PRODUCT APPROVAL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |