Plan Review Notes
Plan Review Notes For Permit 03091654
Permit Number 03091654
Review Stop B
Sequence Number 2
Notes
Date Text
2004-04-08 00:00:00CONTRACTOR BROUGHT BACK PLANS ON 4-8-04.
2003-12-31 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 DETAILS TO COMPLY WITH SEC. 1609.4.3
 FBC 2001, WHICH DOESN'T ALLOW THE
 STEEL STRESS TO BE INCREASED. USE THE
 HIGH WIND RESISTANT CONSTRUCTION
 CATALOGUE BY SIMPSON WHICH IS THE
 CATALOGUE THAT WAS ALREADY REVISED.
 **NOTE: PROVIDE ENGINEERING CALCULATIONS
 FOR VALUES OTHER THAN THOSE PUBLISHED
 ON CATALOGUE. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-REVISE SPECIFICATIONS FOR CEILING
 INSTALLATION AT PORCHES. SEE ASTM
 C-1063. NEED FASTENER THAT PENETRATES
 1 3/4" INTO WOOD.