Plan Review Notes
Plan Review Notes For Permit 03091654
Permit Number 03091654
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO
 THE PLAN FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} USE THE CORRECT LOAD CALCULATION. IF
 USING 220.30,SEE(B)(3) "NAMEPLARE
 RATING OF ALL APPLIANCES". ALSO SEE
 220.16,17 & 18.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE NEW
 PANEL.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210.11-C-3
 MUST BE 20A AND #12AWG.
  
 4} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210.12
  
 5} VERIFY 2/0 FEEDER SIZE FROM THE
 EXISTING PANEL TO 100 AMP DISCONNECT.
  
 6} THE "EXISTING" GEC IS TO SMALL FOR
 THE SERVICE,SHOULD BE 1/0 PER 250.66.
  
 7} VERIFY THAT THE CONDUIT FROM THE
 EXISTING PANEL TO THE 100 AMP
 DISCONNECT DOES NOT NEED AN EQUIPMENT
 GROUND.
  
 8} ADD SMOKE DETECTOR IN THE MASTER
 BEDROOM PER 8-1.4.1.6.2(1),NFPA-72.
  
 9} THE HALL NEEDS A RECEPTACLE PER 210.
 52(H).
  
 10} ADD RECEPTACLES TO THE EXERCISE ROOM
 PER 210.52(A)(1) & (2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718