| Plan Review Notes For Permit 03091654 |
| Permit Number |
03091654 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-10 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO | | | THE PLAN FOR CODE COMPLIANCE AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} USE THE CORRECT LOAD CALCULATION. IF | | | USING 220.30,SEE(B)(3) "NAMEPLARE | | | RATING OF ALL APPLIANCES". ALSO SEE | | | 220.16,17 & 18. | | | | | | 2} PROVIDE A PANEL SCHEDULE FOR THE NEW | | | PANEL. | | | | | | 3} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210.11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 4} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210.12 | | | | | | 5} VERIFY 2/0 FEEDER SIZE FROM THE | | | EXISTING PANEL TO 100 AMP DISCONNECT. | | | | | | 6} THE "EXISTING" GEC IS TO SMALL FOR | | | THE SERVICE,SHOULD BE 1/0 PER 250.66. | | | | | | 7} VERIFY THAT THE CONDUIT FROM THE | | | EXISTING PANEL TO THE 100 AMP | | | DISCONNECT DOES NOT NEED AN EQUIPMENT | | | GROUND. | | | | | | 8} ADD SMOKE DETECTOR IN THE MASTER | | | BEDROOM PER 8-1.4.1.6.2(1),NFPA-72. | | | | | | 9} THE HALL NEEDS A RECEPTACLE PER 210. | | | 52(H). | | | | | | 10} ADD RECEPTACLES TO THE EXERCISE ROOM | | | PER 210.52(A)(1) & (2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|