| Notes |
| Date |
Text |
| 2003-10-31 00:00:00 | DENIED: | | | 1.ENERGY CALCULATION FOR MODEL D ITEM | | | #2. INDICATES "SINGLE FAMILY".SHOULD | | | READ MULTI-FAMILY. | | | | | | 2.NOTE #7, O.A. USING 4% OF OPERABLE | | | WINDOWS.AS PER 2001 FBC(M) 403.3, | | | MULTI-FAMILY IS NOT CONSIDERED ONE AND | | | TWO FAMILY DWELLING (R-3 OCCUPANCY) | | | THEREFORE IS REQUIRED TO MEET THE | | | REQUIREMENTS FOR OUTSIDE AIR AS | | | INDICATED ON TABLE 403.3. | | | | | | 3.RETURN TRANSFER DUCTS ARE NOT SIZED | | | CORRECTLY REFERENCE 2001 FBC(M) 601.4 | | | EXCEPTION #1. (SEE ATTACHED SHEET) |
|