2003-10-07 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE THAT AS OF JULY 1ST,
 2003, WE ARE NOW UNDER THE 2002 NEC.
 PLEASE ADJUST PLANS AND REFERENCES.
  
 2)NOTE: PLEASE SEE THE 2002NEC, 210.12
 IT IS NOT JUST RECEPTS.
  
 3)NOTE: PLEASE CORRELATE RISER AND
 PANEL SCHEDULE FOR A/C COMPRESSOR.
 ONE SHOWS 30A AND OTHER 40A?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717