| Plan Review Notes For Permit 03091366 |
| Permit Number |
03091366 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-10 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE VERFIY EXISTING | | | EQUIPMENT GROUNDING CONDUCTORS FROM | | | 8HA TO TANSFORMER AND FROM TRANSFORMER | | | TO 8LA. 250.110 250.110? | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125%. 230.42,215.3 ETC. | | | | | | 3)NOTE:PLEASE SEE FIRE REVIEW COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|