2003-10-10 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE VERFIY EXISTING
 EQUIPMENT GROUNDING CONDUCTORS FROM
 8HA TO TANSFORMER AND FROM TRANSFORMER
 TO 8LA. 250.110 250.110?
  
 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 AT 125%. 230.42,215.3 ETC.
  
 3)NOTE:PLEASE SEE FIRE REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  