| Plan Review Notes For Permit 03091348 |
| Permit Number |
03091348 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2004-05-08 00:00:00 | **** REDLINED ***** | | | | | | 1)NOTE: NEUTRAL CONDUCTOR FROM METER TO | | | 277/480V PANEL SHOWN AS #4 WHICH IS | | | RATED FOR 85'S PER 310.16 75 DEGREE | | | COL. | | | PLEASE SEE NEUTRAL LOAD EXCEEDS RATING | | | OF AWG. LOAD SHOWN AT 92.5A'S. | | | | | | PLANS NOTED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|