| Plan Review Notes For Permit 03091348 |
| Permit Number |
03091348 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-06 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLANS REQ'D TO BE SIGNED, DATED | | | AND SEALED BY AN ENGINEER. PER FS 471 | | | AND FAC 553.79(6)(A) FOR 277/480V | | | SYSTEMS. | | | | | | 2)NOTE: PLEASE SHOW COMPLETE CONNECTIONS | | | FOR GROUNDING ELECTRODE SYSTEM AND TRANS | | | -FORMER. 250.50 AND 250.30 | | | | | | 3)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | | CONDUCTORS FOR X-FORMER FEED WITH RISER | | | DIAGRAM. ONE SHOWS # 6'S AND OTHER SHOWS | | | #8. | | | | | | 4)NOTE: PLEASE SPECIFY WHAT MATERIALS | | | AND/OR ANY CLASS LOCATIONS FOR STORAGE | | | AREA. PLEASE SEE 384.7/ 110.26 ALSO. | | | AREA ABOUT ELECTRICAL EQUIPMENT SHOULD | | | ALSO HAVE FLR AREA STRIPED FOR REQ'D | | | CLEARENCES TO REMAIN. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|