2003-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) SUBMIT CALCULATIONS FOR ROOF GUTTERS
 AND DOWNSPOUTS PER TABLE 1106.6. SHOW SQ
 FT OF ROOF, & SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN THE
 CALCULATIONS. INDICATE SLOPE OF GUTTER,
 AND SHOW SLOPE OF GUTTER ON PLANS.
 2) DRINKING FOUNTAIN SHALL COMPLY WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS.
 ALSO 11-4.1.3(10)(A) PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. PLEASE SUBMIT A DETAIL.
 3) SEPARATE IRRIGATION PERMIT/PLANS RE-
 QUIRED.
 4) SHT L-1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 5) CERTIFICATE OF AUTHORIZATION REQUIRED
 PER 61G15-23.002(2) FS 471
  