Notes
Date Text
2003-10-14 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE CIRCUIT EM/ EXT LTS PER
 700.12E AND CORRELATE.
  
 2)NOTE: PLEASE CORRELATE A/C SYSTEMS
 AND PANEL SCHEDULES, CIRCUITING SHOWN ON
 PLANS DIFER FROM PANELS.
  
 3)NOTE: PLEASE INCLUDE ALL LICENSE
 INFORMATION ON TITLE BLOCK(CA#) REQ'D
 UNDERFAC 61G15-23.002, FS 471
  
 4)NOTE: PLEASE LABEL ALL DISC MEANS
 AT MAIN.600A,400A,300A ETC. WHICH ONE
 DOES WHICH.? 215.5
  
 5)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL MAINS. 110.9/215.5
  
 6)NOTE: PLEASE PROVIDE LOAD CALCAULTIONS
 WITH ALL CONTINUOUS LOADS AT 125%.
 215.3/230.42 ETC.
  
 7)NOTE: PLEASE PROVIDE INFORMATION FOR
 WIND LOADS ON LIGHT POLES. REQ'D AT THIS
 TIME.
  
 8)NOTE: PLEASE SEE THAT ADDRESS IS REQ`D
 ON PLANS FOR LOCATION OF JOB/SITE.
 61G1-16.004.
  
 PLEASE PROVIDE THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  