| Plan Review Notes For Permit 03091225 |
| Permit Number |
03091225 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-20 00:00:00 | DENIED: | | | 1.PLEASE NOTE, REVISION TO THE 2001 | | | FBC(M) 601.4, EFFECTIVE JUNE 30,2003: | | | | | | BALANCED AIR RETURN - RETURN/TRANSFER | | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM ITS SERVING & THE | | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | | | 2.AS PER 2001 FBC(M) 601.4, FAN SHUT | | | DOWN BY DUCT SMOKE DETECTOR REQUIRED | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS AS PER NFPA 90A | | | 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|