| Plan Review Notes For Permit 03091225 |
| Permit Number |
03091225 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-29 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR | | | INFORMATION REQD' ON TITLE BLOCK FOR | | | ENGINEER OF RECORD. PLEASE INDICATE | | | LICENSE # OF ENG WITH THE CA# WHICH | | | APPEARS TO BE SHOWN. | | | | | | 2)NOTE: PLEASE SEE THAT PLANS REFERENCE | | | THE 1991 LS 101. WE ARE CURRENTLY UNDER | | | THE 1999 LS 101 | | | PLEASE ALSO SEE THAT ELECTRICAL CODES | | | REFERENCED ON PLANS ARE FROM THE 1996 | | | NEC.PLEASE SEE THAT AS OF JULY 1ST,2003 | | | THE STATE HAS ADAOPTED THE 2002 NEC. | | | | | | PLEASE SEE FIRE REVIEW COMMENTS THAT MAY | | | HAVE AN AFECT ON ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|