Plan Review Notes
Plan Review Notes For Permit 03091223
Permit Number 03091223
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-10-02 00:00:001) ON SHEET # 4, NO EXIT SIGNS ARE
 SHOWN AT THE STAIRTOWERS. PLEASE
 EXPLAIN PURPOSE OF EXIT SIGNS THAT
 LEAD PERSONS TO THE ELEVATOR LOBBY.
  
 2) IT DOES NOT APPEAR THAT ANY
 EMERGENCY LIGHTS ARE PRESENT IN THE
 RECEPTION 101 HALLWAY.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910