| Plan Review Notes For Permit 03091212 |
| Permit Number |
03091212 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-23 00:00:00 | PROVISO: | | | PLEASE NOTE, REVISION TO THE 2001 | | | FBC(M) 601.4, EFFECTIVE JUNE 30,2003: | | | | | | BALANCED AIR RETURN - RETURN/TRANSFER | | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM ITS SERVING & THE | | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. | | | | | | 2001 FBC(M)402.3.1(REVISED JUNE 30,2003) | | | BATHROOMS SHALL HAVE A WINDOW WITH A | | | MINIMUM OF 3 SQ FT CLEAR OPENING OR HAVE | | | MECHANICAL VENTILATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|