| | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | 1} THE REFERENCES TO A GENERATOR BACKED |
| | SYSTEM ON E-001 ARE NOT SHOWN ON THE |
| | RISER DIAGRAM. THE PLAN ALSO SHOWS BOTH |
| | HIGH AND LOW VOLTAGE LIGHTS ON THE |
| | EMERGENCY SYSTEM.PLEASE PROVIDE DETAILS |
| | OF THOSE SYSTEMS.(EMERGENCY). |
| | |
| | 2} RESPONSE 1C REGARDING THE CONTRACTOR |
| | TO TAKE LOAD READINGS "AT THE COMPLETION |
| | OF WORK TO ENSURE THAT PANELS ARE NOT |
| | OVERLOADED" IS UNACCEPTABLE. THE DESIGN |
| | PROFESSIONAL SHALL DETERMINE THAT |
| | PANELS ARE NOT OVERLOADED PRIOR TO |
| | BEGINNING WORK. |
| | |
| | 3} PLEASE SEE NOTE #2 FROM LAST REVIEW. |
| | VERIFY CIRCUIT NUMBERS IN THE PANELS AND |
| | ON PLAN. LABEL THE CIRCUITS SO THAT |
| | LOADS CAN BE CORRECTLY CALCULATED. |
| | |
| | 4} THE "ESTIMATED LOADS" ON THE |
| | CALCULATIONS DO NOT REFLECT CONTINUOUS |
| | AND NONCONTINUOUS LOADS PER |
| | 210.19,215.2,215.3, 220.3 OR |
| | 220.3(B)(4).REFER TO WATTAGES OF |
| | RECESSED LUMINAIRES ON SHEET E-002. |
| | |
| | 5} PLEASE SUPPLY A CONTROL DETAIL |
| | SHOWING HOW THE "RELAY" FOR THE |
| | EMERGENCY LIGHTING WILL WORK IN |
| | CONJUNTION WITH SWITCHES AND DIMMERS |
| | SHOWN CONTROLLING EMERGENCY FIXTURES ON |
| | SHEET E-150. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |