| Plan Review Notes For Permit 03091207 |
| Permit Number |
03091207 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-16 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW GROUNDING ATTACHE- | | | -MENT FOR TRANSFORMERS. 250.30 | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM, | | | NOTE MENTIONS TO FEED NEW HV-1 PANEL | | | WITH 200A BRKR. PLEASE CLARIFY,, | | | THERE IS ALREADY ONE "HV-1" PANEL SHOWN | | | ON RISER WITH A 400A FEED? | | | | | | 3)NOTE: PLEASE PROVIDE LOAD CALCULATIONS | | | FOR EXISTING MDP. MDP NOW HAS NEW LOADS | | | ADDED W/OUT SHOWING EXIST. 215.5/ 220 | | | | | | 4)NOTE: PLEASE CLARIFY HEIGHT OF DEVICES | | | FOR ROOMS. ADA | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|