| Plan Review Notes For Permit 03091188 |
| Permit Number |
03091188 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-01-02 00:00:00 | 1) HOW ARE THE TWO EXIT SIGNS LOCATED | | | WITHIN THE WAREHOUSE SEEN AROUND THE | | | STORAGE. ADDITIONAL SIGNS ARE REQUIRED | | | TO DIRECT PERSONS TO THE EXISTING | | | EXIT SIGNS IN WAREHOUSE 115. | | | | | | 2) KNOX-BOX APPLICATIONS CAN BE | | | OBTAINED FROM THE BUREAU OF FIRE | | | PREVENTION AT 835-2910. | | | | | | 3) TAMPER SWITCHES, CHAIN AND LOCK | | | ARE REQUIRED ON FIRE LINE BACKFLOW | | | DEVICE. | | | | | | 4) THE FIRE SPRINKLER PLANS THAT WERE | | | RECENTLY SUBMITTED DID NOT PROVIDE | | | FOR A LARGE ENOUGH SAFETY MARGIN. ALSO | | | TWO HYDRANTS ARE SHOWN ON TWO DIFFERENT | | | PAGES. PLEASE ADVISE HOW THEY ARE | | | BEING SUPPLIED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|