| 2004-01-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:03091188 |
| | ADD: 2951 ELECTRONIC WAY |
| | CONT: ANDERSON-MOORE |
| | TEL: (561)753-7400 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 3ND REVIEW |
| | ACTION: DENIED |
| | 1)106.4.2 STORAGE & FACTORY- INDUS- |
| | TRIAL OCCUPANCIES. IT SHALL BE THE |
| | RESPONSIBILITY OF THE OWNER, AGENT, |
| | PROPIETOR OR OCCUPANT OF GROUP S AND |
| | GROUP F OCCUPANCIES, OR ANY OCCUPANCY |
| | WHERE EXCESSIVE FLOOR LOADING IS LIKELY |
| | TO OCCUR, TO EMPLOY A COMPETENT ARCHI- |
| | TECT OR ENGINEER IN COMPUTING THE SAFE |
| | FLOOR LOAD CAPACITY. ALL SUCH COMPUTA- |
| | TIONS SHALL BE ACCOMPANIED BY AN AFFA- |
| | DAVIT FROM THE ARCHITECT OR ENGINEER |
| | STATING THE SAFE ALLOWABLE FLOOR LOADS |
| | ON EACH FLOOR IN POUNDS PER SQ FT.THE |
| | COMPUTATIONS & AFFADAVIT SHALL BE FILED |
| | AS A PERMANENT RECORD OF THE BLDG DEPT. |
| | SHOW CALCULATIONS FOR THE FLOOR LOADS |
| | OF THE MEZZANINE FLOOR OR DELETE ALL REF |
| | RENCES OF A MEZZANINE FROM PLAN. |
| | 2) NOTE: SHEET A6.2 AS WELL AS THE |
| | PRODUCT APPROVAL INDICATE THAT THE OVER- |
| | HEAD DOORS WILL HAVE GLAZED PANELS, NO |
| | INFORMATION ON THE LARGE MISSLE IMPACT |
| | TESTING FOR GLAZED UNITS. SHUTTERS WILL |
| | BE REQUIRED. |
| | 3) THE PLANS INDICATE THAT THIS STOR- |
| | AGE BUILDING WILL BE FULLY SPRINKLERED, |
| | TO MEET THE DESIGN CRITERIA TABLE 500 |
| | THIS IS TRUE, NO FIRE SPRINKLER PLANS |
| | HAVE BEEN PROVIDED AAS PART OF THIS |
| | BUILDING SET OF PLANS. EVEN THOUGH A SEP |
| | ERATE FIRE SPINKLER PERMIT IS APPLIED |
| | FOR FIRE SPRINKLER PLANS ARE REQUIRED |
| | FOR THE BUILDING PERMIT SET. PLANS NEED |
| | TO SHOW FIRE SPRINKLER DESIGN FOR TYPE |
| | OCCUPANCY, STORAGE, HAZARD (S1/S2) 903. |
| | |
| | 4) THIS BUILDING ALSO QUALIFIES FOR |
| | A RESIDENT INSPECTOR UNDER THE CITIES |
| | CRITERIA FOR RESIDENT INSPECTORS. WEST |
| | PALM BEACH ADMINISTRATIVE CODE 105.3(5) |
| | BUILDINGS GREATER THAN 20,000 SQ. FT. |
| | THREE (3) SETS OF PLANS, PRODUCT |
| | APPROVALS OR OTHER RELATED DOCUMENTS ARE |
| | REQUIRED BEFORE ISSUANCE OF A PERMIT. |
| | BUILDING PLAN REVIEW |