2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-7.2 DETAILS FOR ACCESSIBLE
 FIXTURES REQUIRES MORE INFORMATION. SEE
 RED LINE CORRECTIONS AND PUT ON PLANS.
 2) WATER RISER DIAGRAM. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. - ALL CHANGES
 TO A SIGNED AND SEALED PLANS SHALL BE
 APPROVED BY THE ARCHITECT OF RECORD.
 3) SHT P-1 SANITARY RISER DIAGRAM. IN-
 DIRECT WASTE FROM THE WATER HEATER SHALL
 DRAIN INTO A FLOOR SINK. FLOOR DRAIN ARE
 NOT AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTION 802.3 - ALL CHANGES TO A SIGNED
 AND SEALED PLAN SHALL BE APPROVED BY THE
 ARCHITECT OF RECORD. (SEE PEN CHANGES TO
 SANT. AND WATER RISER DIAGRAMS.
  
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  