Text |
| 2003-12-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A-7.2 DETAILS FOR ACCESSIBLE |
| | FIXTURES REQUIRES MORE INFORMATION. SEE |
| | RED LINE CORRECTIONS AND PUT ON PLANS. |
| | 2) WATER RISER DIAGRAM. WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIX- |
| | TURES IN AN "EFFECTIVE RANGE" NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. - ALL CHANGES |
| | TO A SIGNED AND SEALED PLANS SHALL BE |
| | APPROVED BY THE ARCHITECT OF RECORD. |
| | 3) SHT P-1 SANITARY RISER DIAGRAM. IN- |
| | DIRECT WASTE FROM THE WATER HEATER SHALL |
| | DRAIN INTO A FLOOR SINK. FLOOR DRAIN ARE |
| | NOT AN APPROVED INDIRECT WASTE RECEPTOR. |
| | SECTION 802.3 - ALL CHANGES TO A SIGNED |
| | AND SEALED PLAN SHALL BE APPROVED BY THE |
| | ARCHITECT OF RECORD. (SEE PEN CHANGES TO |
| | SANT. AND WATER RISER DIAGRAMS. |
| | |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |