Plan Review Notes
Plan Review Notes For Permit 03091188
Permit Number 03091188
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE FACILITIES PER TABLE 403.1 (PLUMB),
 AND TABLE 1003.1 (BLDG). SHOW SQUARE
 FOOTAGE FOR EACH OCCUPANCY. A DRINKING
 FOUNTAIN AND SERVICE SINK ARE REQUIRED
 PER TABLE 403.1
 2) IF BATHING FACILITIES ARE PROVIDED ON
 A SITE, THEN EACH SUCH PUBLIC OR COMMON
 BATHING FACILITY SHALL COMPLY WITH SECT-
 ION 11-4.23 AND ALL SUBSECTIONS. SECTION
 11-4.1.2(6). (ROOM 108)
 3) IN NEW CONSTRUCTION, A LAV SHALL BE
 PROVIDED WITHIN THE ACCESSIBLE TOILET
 STALL. SEE FIGURE 30E
 4) SHT AW.4 SUBMIT CALCULATIONS FOR GUT-
 TERS AND DOWNSPOUTS. SHOW SQUARE FOOTAGE
 FOR EACH AREA OF ROOF & SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS IN
 CALCULATIONS. INDICATE SIZE OF GUTTERS
 AND DOWNSPOUTS.
 5) SHT A7.2 DETAIL #3, BREAKROOM SINK
 SHALL COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. PROVIDE A DETAIL.
 6) ACCESSIBLE URNAL SHALL COMPLY WITH
 SECTION 11-4.18 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL, AND SHOW CLEAR FLOOR
 SPACE.
 7) WATER RISER DIAGRAM REQUIRED. SECTION
 104.3.1.1
 8) SHT P-1 SANITARY RISER DIAGRAM, IN-
 DICATE TYPE OF DRAIN THE W/HEATER IS
 DRAINING INTO. AN INDIRECT WASTE SHALL
 BE REQUIRED FOR PAN DRAIN AND T/P RELIEF
 VALVE DRAIN. SECTION 802.3 & 802.3.2
 9) INDICATE TYPE AND AMOUNT OF MATERIAL
 BEING STORED IN THE WAREHOUSE. FUTURE
 COMMENTS MAY ARISE DEPENDING ON RESPONSE
 TO THIS QUESTION.
  
 ---------WHEN RESUBMITTING PLANS--------
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved