| Date |
Text |
| 2003-10-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | |
| | 1) SUBMIT CALCULATIONS FOR MINIMUM FIX- |
| | TURE FACILITIES PER TABLE 403.1 (PLUMB), |
| | AND TABLE 1003.1 (BLDG). SHOW SQUARE |
| | FOOTAGE FOR EACH OCCUPANCY. A DRINKING |
| | FOUNTAIN AND SERVICE SINK ARE REQUIRED |
| | PER TABLE 403.1 |
| | 2) IF BATHING FACILITIES ARE PROVIDED ON |
| | A SITE, THEN EACH SUCH PUBLIC OR COMMON |
| | BATHING FACILITY SHALL COMPLY WITH SECT- |
| | ION 11-4.23 AND ALL SUBSECTIONS. SECTION |
| | 11-4.1.2(6). (ROOM 108) |
| | 3) IN NEW CONSTRUCTION, A LAV SHALL BE |
| | PROVIDED WITHIN THE ACCESSIBLE TOILET |
| | STALL. SEE FIGURE 30E |
| | 4) SHT AW.4 SUBMIT CALCULATIONS FOR GUT- |
| | TERS AND DOWNSPOUTS. SHOW SQUARE FOOTAGE |
| | FOR EACH AREA OF ROOF & SHOW 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS IN |
| | CALCULATIONS. INDICATE SIZE OF GUTTERS |
| | AND DOWNSPOUTS. |
| | 5) SHT A7.2 DETAIL #3, BREAKROOM SINK |
| | SHALL COMPLY WITH SECTION 11-4.24 AND |
| | ALL SUBSECTIONS. PROVIDE A DETAIL. |
| | 6) ACCESSIBLE URNAL SHALL COMPLY WITH |
| | SECTION 11-4.18 AND ALL SUBSECTIONS. |
| | SUBMIT A DETAIL, AND SHOW CLEAR FLOOR |
| | SPACE. |
| | 7) WATER RISER DIAGRAM REQUIRED. SECTION |
| | 104.3.1.1 |
| | 8) SHT P-1 SANITARY RISER DIAGRAM, IN- |
| | DICATE TYPE OF DRAIN THE W/HEATER IS |
| | DRAINING INTO. AN INDIRECT WASTE SHALL |
| | BE REQUIRED FOR PAN DRAIN AND T/P RELIEF |
| | VALVE DRAIN. SECTION 802.3 & 802.3.2 |
| | 9) INDICATE TYPE AND AMOUNT OF MATERIAL |
| | BEING STORED IN THE WAREHOUSE. FUTURE |
| | COMMENTS MAY ARISE DEPENDING ON RESPONSE |
| | TO THIS QUESTION. |
| | |
| | ---------WHEN RESUBMITTING PLANS-------- |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |