| Plan Review Notes For Permit 03091188 |
| Permit Number |
03091188 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-15 00:00:00 | DENIED:NO MECHANICAL PLANS SUBMITTED | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION: | | | 1. PLEASE PROVIDE ENERGY CALCULATIONS | | | AS PER 2001 FBC CHAPTER 13 | | | | | | 2. PLEASE INDICATE WHAT WILL BE STORED | | | IN THE WAREHOUSE. | | | | | | 3. PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 2001 FBC(M) TABLE 403.3. | | | | | | 4. FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | REQUIRED WITH NOTIFICATION TO ALARM/ | | | STROBE IN NORMALLY OCCUPIED AREAS. | | | 2001 FBC(M) 606.2.1, 606.4.1 & NFPA 90A | | | 4-4.4.3. | | | | | | 5. PROVIDE PLANS INDICATING DUCT LAYOUT, | | | SIZE AND MATERIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|