2003-10-02 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3) PLEASE EXPLAIN HOW FIRE AND
 PARAMEDICAL EQUIPMENT EXPECTED TO
 PASS THRU THE SLIDING GATES. WHAT
 PROVISIONS WILL BE MADE FOR ACCESS.
 IF ELECTRIC WHAT HAPPENS, WHEN LOSS
 OF POWER OCCURS.
  
 4) A KNOX-BOX WILL BE REQUIRED FOR
 ACCESS INTO THE BUILDING.
  
 5) NO FIRE SPRINKLER PLANS PROVIDED.
  
 6) PLEASE EXPLAIN TYPES OF STORAGE THAT
 WILL BE CONTAINED IN WAREHOUSE 115.
 ALSO PLEASE INCLUDE
  
 7) IT APPEARS THAT ALL OF THE EMERGENCY
 LIGHTS ARE PRESENT ON THE OUTSIDE
 WALLS OF WAREHOUSE 115. WHY ARE NONE
 SHOWN ON FOR THE MAIN AISLE.
  
 8) THE FIRE ALARM SYSTEM SINCE
 PERMITTED AFTER 8.1.03 IS REQUIRED TO
 BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 9) HOW IS EXITING MAINTAINED FROM
 WAREHOUE 115 INTO THE LOADING DOCK
 AREA. HOW IS THE AISLE GOING TO
 BE MAINTAINED.
  
 10) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR MEZZANINE
 STAIR HANDRAILS AND GUARDRAILS.
  
 11) PLEASE EXPLAIN ELECTRIC STRIKES AND
 HOW THEY EFFECT EXIT ACCESS, NEAR
 CORRIDOR 104 EXIT DOOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL