Plan Review Notes
Plan Review Notes For Permit 03091188
Permit Number 03091188
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-10 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTE ON RISER NEXT TO
 PANEL OF, MENTIONS TO SEE TYP PANEL
 SCHEDULE ON E-4? PLEASE CLARIFY?
  
 2)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDING BETWEEN PANELS AND ALL
 OTHER EQUIPMENT. 250.110/ SIZE PER
 250.122.
  
 3)NOTE: PLEASE CLARIFY CONDUCTORS FOR
 PANEL A/C? RISER SHOWS 350MCM BUT NOT
 HOW MANY? PLEASE ALSO SEE MDP, SHOWS
 500MCM FOR CONDUCTOR SIZE.
 PLEASE ALSO SEE, PANEL SHOWS NEUTRAL AS
 -0-. PLEASE SEE THAT A NEUTRAL CONDUCTO
 WILL BE REQ'D TO TERMINATE AT A/C PANEL.
  
 4)NOTE: PLEASE SEE THAT LOAD CALCULATION
 -S ARE MISSING AND SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 2203,10,11,13 ETC 230.42, 215.3
  
 5)NOTE: PLEASE PROVIDE MIN WIND LOADS
 FOR LT POLE UNDER FBC. MIN 140MPH
  
 PLEASE SEE OTHER REVIEWERS COMMENTS THAT
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  