| Plan Review Notes For Permit 03091188 |
| Permit Number |
03091188 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-10 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE NOTE ON RISER NEXT TO | | | PANEL OF, MENTIONS TO SEE TYP PANEL | | | SCHEDULE ON E-4? PLEASE CLARIFY? | | | | | | 2)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | -MENT GROUNDING BETWEEN PANELS AND ALL | | | OTHER EQUIPMENT. 250.110/ SIZE PER | | | 250.122. | | | | | | 3)NOTE: PLEASE CLARIFY CONDUCTORS FOR | | | PANEL A/C? RISER SHOWS 350MCM BUT NOT | | | HOW MANY? PLEASE ALSO SEE MDP, SHOWS | | | 500MCM FOR CONDUCTOR SIZE. | | | PLEASE ALSO SEE, PANEL SHOWS NEUTRAL AS | | | -0-. PLEASE SEE THAT A NEUTRAL CONDUCTO | | | WILL BE REQ'D TO TERMINATE AT A/C PANEL. | | | | | | 4)NOTE: PLEASE SEE THAT LOAD CALCULATION | | | -S ARE MISSING AND SHOW ALL CONTINUOUS | | | LOADS AND LARGEST MOTOR LOADS AT 125%. | | | 2203,10,11,13 ETC 230.42, 215.3 | | | | | | 5)NOTE: PLEASE PROVIDE MIN WIND LOADS | | | FOR LT POLE UNDER FBC. MIN 140MPH | | | | | | PLEASE SEE OTHER REVIEWERS COMMENTS THAT | | | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|