| 2004-12-01 00:00:00 | ********** UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE LOAD CALCULATIONS | | | NEED TO MEET NEC 220.31 | | | PLEASE SEE A/C LOAD IS NOT DERATED W/ | | | GEN LT LOAD. | | | | | | 2)NOTE: PLEASE SEE AREAS ON PLANS WHERE | | | CHANGES HAVE BEEN MADE ARE INITIALED AND | | | DO NOT CORRELATE WITH OTHER INITIALS OR | | | SIGNATURE FROM ARCHITECT. THESE ARE | | | SIGNED AND SEALED PLANS BY AN ARCHITECT | | | AND THAT PERSON IS THE ONLY ONE | | | PERMITTED TO MAKE ANY CHANGES. | | | FS 481.221 | | | | | | 3)NOTE: PLEASE SEE 210.8A6. ALL RECEPTS | | | ON KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | ALSO 210.52C1 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|