Plan Review Notes
Plan Review Notes For Permit 03091176
Permit Number 03091176
Review Stop E
Sequence Number 3
Notes
Date Text
2004-12-01 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 NEED TO MEET NEC 220.31
 PLEASE SEE A/C LOAD IS NOT DERATED W/
 GEN LT LOAD.
  
 2)NOTE: PLEASE SEE AREAS ON PLANS WHERE
 CHANGES HAVE BEEN MADE ARE INITIALED AND
 DO NOT CORRELATE WITH OTHER INITIALS OR
 SIGNATURE FROM ARCHITECT. THESE ARE
 SIGNED AND SEALED PLANS BY AN ARCHITECT
 AND THAT PERSON IS THE ONLY ONE
 PERMITTED TO MAKE ANY CHANGES.
 FS 481.221
  
 3)NOTE: PLEASE SEE 210.8A6. ALL RECEPTS
 ON KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 ALSO 210.52C1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]