Plan Review Notes
Plan Review Notes For Permit 03091176
Permit Number 03091176
Review Stop B
Sequence Number 2
Notes
Date Text
2004-06-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PERMIT APPLICATION IS EXPIRED,
 FBC104.1.6.SUBMIT A NEW PERMIT
 APPLICATION.
  
 2.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (OVER 90 DAYS WITHOUT
 COMMENCING WORK, FS 713.13).
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)DETAILS 7-A5 AND 1-A5, SPECIFY
 WHICH CONNECTORS ARE TO BE USED.
 FASTENING CANNOT CONFLICT WITH THE
 MANUFACTURER'S CATALOG.
  
 5.)CITY OF WPB AMENDMENTS TO THE
 FBC 1804.1.7, THE LOWEST BUILDING
 FLOOR ELEVATION AT THE PERIMETER OF
 A MONOLOTHIC FOUNDATION AT HABITABLE
 AREAS SHALL BE A MINIMUM OF 4" ABOVE THE
 FINISHED GRADE.FBC1804.1.3, THE
 BOTTOM OF FOUNDATIONS SHALL EXTEND NO
 LESS THAN 12" BELOW FINISH GRADE.
 REVISE 7-A5 TO SHOW GRADE AND COMPLIANCE
 WITH THE TWO CODES REFERENCED.
  
 6.)THE IMPACT FEE DOCUMENTATION
 INDICATES NO SQUARE FOOTAGE BEING
 ADDED.THIS IS AN ADDITION OF 150
 SQUARE FEET.PLEASE CONTACT 233-5025.
  
 7.)THE AREA CALCS PREPARED BY THE
 ARCHITECT SHOW AN ADDITION OF 150 SQUARE
 FEET, THE THE ENERGY CALCS SHOW 175.
 BOTH MUST BE CONSISTENT.SIGN THE
 OWNER/AGENT LINE OF THE ENERGY CALC.
 SUBMIT TWO COPIES.
  
 8.)PRODUCT APPROVALS REQUIRED FOR
 THE FRENCH DOORS, WINDOWS AND IMPACT
 PROTECTION.TWO COPIES OF EACH ARE
 REQUIRED.FLORIDA STATEWIDE, LOCAL OR
 SITE SPECIFIC PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE TEST REPORT FAC9B72.
 WWW.FLORIDABUILDING.ORG