| 2004-06-29 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE PERMIT APPLICATION IS EXPIRED, |
| | FBC104.1.6.SUBMIT A NEW PERMIT |
| | APPLICATION. |
| | |
| | 2.)THE NOTICE OF COMMENCEMENT IS |
| | EXPIRED (OVER 90 DAYS WITHOUT |
| | COMMENCING WORK, FS 713.13). |
| | |
| | 3.)SEPARATE PERMITS REQUIRED. |
| | |
| | 4.)DETAILS 7-A5 AND 1-A5, SPECIFY |
| | WHICH CONNECTORS ARE TO BE USED. |
| | FASTENING CANNOT CONFLICT WITH THE |
| | MANUFACTURER'S CATALOG. |
| | |
| | 5.)CITY OF WPB AMENDMENTS TO THE |
| | FBC 1804.1.7, THE LOWEST BUILDING |
| | FLOOR ELEVATION AT THE PERIMETER OF |
| | A MONOLOTHIC FOUNDATION AT HABITABLE |
| | AREAS SHALL BE A MINIMUM OF 4" ABOVE THE |
| | FINISHED GRADE.FBC1804.1.3, THE |
| | BOTTOM OF FOUNDATIONS SHALL EXTEND NO |
| | LESS THAN 12" BELOW FINISH GRADE. |
| | REVISE 7-A5 TO SHOW GRADE AND COMPLIANCE |
| | WITH THE TWO CODES REFERENCED. |
| | |
| | 6.)THE IMPACT FEE DOCUMENTATION |
| | INDICATES NO SQUARE FOOTAGE BEING |
| | ADDED.THIS IS AN ADDITION OF 150 |
| | SQUARE FEET.PLEASE CONTACT 233-5025. |
| | |
| | 7.)THE AREA CALCS PREPARED BY THE |
| | ARCHITECT SHOW AN ADDITION OF 150 SQUARE |
| | FEET, THE THE ENERGY CALCS SHOW 175. |
| | BOTH MUST BE CONSISTENT.SIGN THE |
| | OWNER/AGENT LINE OF THE ENERGY CALC. |
| | SUBMIT TWO COPIES. |
| | |
| | 8.)PRODUCT APPROVALS REQUIRED FOR |
| | THE FRENCH DOORS, WINDOWS AND IMPACT |
| | PROTECTION.TWO COPIES OF EACH ARE |
| | REQUIRED.FLORIDA STATEWIDE, LOCAL OR |
| | SITE SPECIFIC PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE TEST REPORT FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |