| Plan Review Notes For Permit 03091152 |
| Permit Number |
03091152 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-14 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND | | | FS 481 FOR MISSING INFORMATION REQ'D ON | | | TITLE BLOCK. | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE(S). 215.5 | | | | | | 3)NOTE: PLEASE CLARIFY SITE/PARKING | | | EGRESS LIGHTING FOR HOUSE PANEL? | | | LS 101 5-8 | | | | | | 4)NOTE: PLEASE SHOW CIRCUITING FOR | | | EM/ EXT LTS PER 700.12E. | | | | | | 5)NOTE: PLEASE COMPLETE RISER DIAGRAM, | | | MAINS, PANELS, DISC'S ALL WIRE SIZES,ETC | | | PLEASE INCLUDE LOAD CALCULATIONS FOR | | | SERVICE. VOLTAGE, AIC RATINGS ETC ETC. | | | 215.5 | | | | | | 6)NOTE: PLEASE SIGN, DATE AND SEAL ALL | | | SHEETS AS REQ'D UNDER FS 481.221. | | | | | | PLEASE NOTE, UNABLE TO DO FULL REVIEW, | | | DUE TO PLANS NOT BEING FULLY COMPLETE AT | | | THIS TIME. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|