| Plan Review Notes For Permit 03091147 |
| Permit Number |
03091147 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-01-02 00:00:00 | 1) FIRE ALARM RISER, NOTE # 5 IS | | | NOT CORRECT. DUCT DETECTORS SHALL | | | CAUSE AN ALARM NOT A SUPERVISORY | | | SIGNAL. | | | | | | 2) FIRE SPRINKLER PLANS ARE REQUIRED | | | AT TIME OF PERMIT APPLICATION. FIRE | | | SPRINKLER SHOP DRAWINGS CAN BE | | | SUBMITTED LATER BUT INITIAL DESIGN | | | DRAWINGS ARE REQUIRED. | | | | | | 3) BUILDING OFFICIAL'S APPROVAL IS | | | REQUIRED TO USE DELUGE FIRE SPRINKLER | | | HEADS IN LIEU OF OPENING PROTECTIVES. | | | PREVIOUS EXAMPLES CITED, FIRST WENT | | | TO THE CONSTRUCTION BOARD OF ADJUSTMENT | | | AND APPEALS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|