Plan Review Notes
Plan Review Notes For Permit 03091147
Permit Number 03091147
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2004-01-02 00:00:001) FIRE ALARM RISER, NOTE # 5 IS
 NOT CORRECT. DUCT DETECTORS SHALL
 CAUSE AN ALARM NOT A SUPERVISORY
 SIGNAL.
  
 2) FIRE SPRINKLER PLANS ARE REQUIRED
 AT TIME OF PERMIT APPLICATION. FIRE
 SPRINKLER SHOP DRAWINGS CAN BE
 SUBMITTED LATER BUT INITIAL DESIGN
 DRAWINGS ARE REQUIRED.
  
 3) BUILDING OFFICIAL'S APPROVAL IS
 REQUIRED TO USE DELUGE FIRE SPRINKLER
 HEADS IN LIEU OF OPENING PROTECTIVES.
 PREVIOUS EXAMPLES CITED, FIRST WENT
 TO THE CONSTRUCTION BOARD OF ADJUSTMENT
 AND APPEALS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910