| Plan Review Notes For Permit 03091147 |
| Permit Number |
03091147 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-11-14 00:00:00 | 1) DUCT DETECTORS SHALL INTITIATE AN | | | ALARM NOT SUPERVISORY SIGNAL AS | | | INDICATED ON SHEET E-4. | | | | | | 2) PLEASE EXPLAIN SINGLE EXIT THEORY | | | FROM SECOND FLOOR. THE FLOOR PLAN | | | DIFFERS FROM EXIT SIGN PLAN. | | | | | | 3) FUTURE KITCHEN EXHAUST FAN SHALL | | | BE A MINIMUM OF 10 FEET FROM ANY | | | MAKE-UP AIR LOCATIONS. | | | | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | | | | 5) PLEASE SEE COMMENTS REGARDING EXITS, | | | EXIT PASSAGEWAYS, PROVIDED BY ROBERT | | | BROWN, BUILDING PLAN REVIEWER. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|