2003-11-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.NOTE THE
 COMMENTS LISTED BELOW AS 'NOT ADDRESSED'
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 10/21/03:
  
 2) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-103.1.1.1THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN SHEET 2 OF THE
 ENERGY CODE COMPLIANCE FORM, TO CERTIFY
 COMPLIANCE.
  
 3) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1010.1.1TWO EXITS ARE REQUIRED
 FROM EACH STOREY (REF: FBC 1004.1.2).
 THE SECOND FLOOR DOES NOT HAVE AN EXIT
 DIRECTLY CONNECTED TO A PUBLIC WAY (REF:
 FBC 1010.1.1) SO THE FIRST FLOOR
 ELEVATOR LOBBY AT STAIR #1 MUST MEET THE
 REQUIREMENTS OF AN EXIT PASSAGEWAY OR
 VESTIBULE (REF: FBC 1010.1.1).AS THE
 DEPTH OF THE FIRST FLOOR ELEVATOR LOBBY
 FROM THE FRONT OF THE BUILDING EXCEEDS
 10 FEET, THAT LOBBY MUST MEET THE
 RREQUIREMENTS OF AN EXIT PASSAGEWAY.AN
 EXIT PASSAGEWAY SHALL NOT HAVE ANY
 OPENINGS OTHER THAN THE REQUIRED EXIT
 DOORS, SO THE ELEVATOR AND ELEVATOR
 MACHINE ROOM SHALL NOT BE ACCESSED FROM
 THIS SPACE.
  
 4) FBC 1006.2.4EXTERIOR STAIRWAY.
 SHEET A3.2, EAST ELEVATION,THE EXIT
 DISCHARGE ROUTE PASSES THE NEW FIRST
 FLOOR EXIT DOORS SO THESE SHALL BE MIN.
 1-HOUR DOOR ASSEMBLIES.AMEND/ANNOTATE
 THE PLANS.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 705.1.1.2SHEET A3.2, SOUTH
 ELEVATION.THIRD FLOOR REPLACEMENT
 WINDOWS.SEE PREVIOUS PLAN REVIEW.
  
 7) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-1, FOUNDATION PLAN - NEW FOOTERS
 SEE PREVIOUS PLAN REVIEW.
  
 8) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-1, 2ND FLOOR FRAMING PLAN -
 REINFORCEMENT.SEE PREVIOUS PLAN REVIEW
  
 9) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-1, 2ND FLOOR FRAMING PLAN -
 LANDING SLAB.SEE PREVIOUS PLAN REVIEW.
  
 10) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-4STAIR SECTION - MONOLITHIC
 FOOTING.SEE PREVIOUS PLAN REVIEW.
  
 11) THIS COMMENT HAS NOT BEEN ADDRESSED.
 PROVIDE ELEVATIONAL VIEW OF DETAIL 1/S-1
 SEE PREVIOUS PLAN REVIEW.
  
 12) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-5OUTDATED REFERENCE STANDARDS
 SEE PREVIOUS PLAN REVIEW.
  
 13) THIS COMMENT HAS NOT BEEN ADDRESSED.
 DOOR, WINDOW, STOREFRONT AND SHUTTER
 PRODUCT APPROVALS.SEE PREVIOUS PLAN
 REVIEW.
  
 14) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT A ROOFING SYSTEM PRODUCT APPROVAL
 SEE PREVIOUS PLAN REVIEW.
  
 15) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 11-4.1.3(11)ACCESSIBLE TOILET
 FACILITIES.SEE PREVIOUS PLAN REVIEW.
  
 16) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS