| 2003-11-12 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | NOTE: |
| | CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| | STATES THAT A LOCAL GOVERNMENT SHALL |
| | IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| | OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION.NOTE THE |
| | COMMENTS LISTED BELOW AS 'NOT ADDRESSED' |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 10/21/03: |
| | |
| | 2) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC 13-103.1.1.1THE PROFESSIONALS |
| | RESPONSIBLE FOR THE DESIGN OF THE |
| | BUILDING SHELL AND THE ELECTRICAL, |
| | LIGHTING, MECHANICAL AND PLUMBING |
| | SYSTEMS SHALL EACH SIGN SHEET 2 OF THE |
| | ENERGY CODE COMPLIANCE FORM, TO CERTIFY |
| | COMPLIANCE. |
| | |
| | 3) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC 1010.1.1TWO EXITS ARE REQUIRED |
| | FROM EACH STOREY (REF: FBC 1004.1.2). |
| | THE SECOND FLOOR DOES NOT HAVE AN EXIT |
| | DIRECTLY CONNECTED TO A PUBLIC WAY (REF: |
| | FBC 1010.1.1) SO THE FIRST FLOOR |
| | ELEVATOR LOBBY AT STAIR #1 MUST MEET THE |
| | REQUIREMENTS OF AN EXIT PASSAGEWAY OR |
| | VESTIBULE (REF: FBC 1010.1.1).AS THE |
| | DEPTH OF THE FIRST FLOOR ELEVATOR LOBBY |
| | FROM THE FRONT OF THE BUILDING EXCEEDS |
| | 10 FEET, THAT LOBBY MUST MEET THE |
| | RREQUIREMENTS OF AN EXIT PASSAGEWAY.AN |
| | EXIT PASSAGEWAY SHALL NOT HAVE ANY |
| | OPENINGS OTHER THAN THE REQUIRED EXIT |
| | DOORS, SO THE ELEVATOR AND ELEVATOR |
| | MACHINE ROOM SHALL NOT BE ACCESSED FROM |
| | THIS SPACE. |
| | |
| | 4) FBC 1006.2.4EXTERIOR STAIRWAY. |
| | SHEET A3.2, EAST ELEVATION,THE EXIT |
| | DISCHARGE ROUTE PASSES THE NEW FIRST |
| | FLOOR EXIT DOORS SO THESE SHALL BE MIN. |
| | 1-HOUR DOOR ASSEMBLIES.AMEND/ANNOTATE |
| | THE PLANS. |
| | |
| | 6) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC 705.1.1.2SHEET A3.2, SOUTH |
| | ELEVATION.THIRD FLOOR REPLACEMENT |
| | WINDOWS.SEE PREVIOUS PLAN REVIEW. |
| | |
| | 7) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SHEET S-1, FOUNDATION PLAN - NEW FOOTERS |
| | SEE PREVIOUS PLAN REVIEW. |
| | |
| | 8) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SHEET S-1, 2ND FLOOR FRAMING PLAN - |
| | REINFORCEMENT.SEE PREVIOUS PLAN REVIEW |
| | |
| | 9) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SHEET S-1, 2ND FLOOR FRAMING PLAN - |
| | LANDING SLAB.SEE PREVIOUS PLAN REVIEW. |
| | |
| | 10) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SHEET S-4STAIR SECTION - MONOLITHIC |
| | FOOTING.SEE PREVIOUS PLAN REVIEW. |
| | |
| | 11) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | PROVIDE ELEVATIONAL VIEW OF DETAIL 1/S-1 |
| | SEE PREVIOUS PLAN REVIEW. |
| | |
| | 12) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SHEET S-5OUTDATED REFERENCE STANDARDS |
| | SEE PREVIOUS PLAN REVIEW. |
| | |
| | 13) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | DOOR, WINDOW, STOREFRONT AND SHUTTER |
| | PRODUCT APPROVALS.SEE PREVIOUS PLAN |
| | REVIEW. |
| | |
| | 14) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SUBMIT A ROOFING SYSTEM PRODUCT APPROVAL |
| | SEE PREVIOUS PLAN REVIEW. |
| | |
| | 15) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC 11-4.1.3(11)ACCESSIBLE TOILET |
| | FACILITIES.SEE PREVIOUS PLAN REVIEW. |
| | |
| | 16) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |