| Plan Review Notes For Permit 03091147 |
| Permit Number |
03091147 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1) PROVIDE SANITARY, WATER, AND STORM | | | ISOMETRIC RISER DIAGRAMS. | | | 2) RPZ BACKFLOWS REQUIRED ON WATER SERV- | | | ICES. | | | 3) SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS PER SECTIONS 1106 | | | AND 1107 AND ALL SUBSECTIONS. SHOW AREA | | | OF ROOF AND SHOW 1/2 AREA OF ALL VERTIC- | | | AL WALLS INCLUDING PARAPETS BEING ADDED | | | AND SHOW AREA OF ROOFS THAT DRAIN ONTO | | | THE ROOF FROM ABOVE. | | | 4) THIS PERMIT IS BEING REVIEWED AS A | | | SHELL AND MINIMUM FIXTURES REQUIRED BY | | | TABLE 403.1 SHALL BE DETERMINED AT THE | | | TIME OF TENANT BUILD-OUT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|