2003-10-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) PROVIDE SANITARY, WATER, AND STORM
 ISOMETRIC RISER DIAGRAMS.
 2) RPZ BACKFLOWS REQUIRED ON WATER SERV-
 ICES.
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW AREA
 OF ROOF AND SHOW 1/2 AREA OF ALL VERTIC-
 AL WALLS INCLUDING PARAPETS BEING ADDED
 AND SHOW AREA OF ROOFS THAT DRAIN ONTO
 THE ROOF FROM ABOVE.
 4) THIS PERMIT IS BEING REVIEWED AS A
 SHELL AND MINIMUM FIXTURES REQUIRED BY
 TABLE 403.1 SHALL BE DETERMINED AT THE
 TIME OF TENANT BUILD-OUT.
  
 REVIEW BY KEN STEVENS