| Plan Review Notes For Permit 03091147 |
| Permit Number |
03091147 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-14 00:00:00 | DENIED: | | | 1.FIRE DAMPERS REQUIRED AT THE FLOOR | | | PENETRATION 1ST FLOOR TO 2ND FLOOR FROM | | | AHU-1. | | | | | | 2.FIRE DAMPERS ALSO REQUIRED AT 2ND | | | FLOOR MECHANICAL CLOSET ON BOTH SUPPY | | | DUCTS. | | | | | | 3.FIRE DAMPER ALSO REQUIRED AT 1ST | | | FLOOR SUPPLY DUCT PENETRATING WALL AT | | | THE ELEVATOR LOBBY. | | | | | | 4.ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPPRESSION AND WALK-IN | | | COOLERS/FREEZERS.PLEASE PROVIDE PLANS | | | AND MANUFACTURER SUBMITTAL DATA WITH | | | PERMIT APPLICATIONS. | | | | | | 5.PLEASE NOTE, A MINIMUM OF 10 FT | | | SEPARATION BETWEEN HOOD EXHAUST AND ANY | | | FRESH AIR INTAKE, PROPERTY LINE OR | | | ADJACENT BUILDINGS. NFPA 96 4-8.2.1 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|