2003-10-14 00:00:00DENIED:
 1.FIRE DAMPERS REQUIRED AT THE FLOOR
 PENETRATION 1ST FLOOR TO 2ND FLOOR FROM
 AHU-1.
  
 2.FIRE DAMPERS ALSO REQUIRED AT 2ND
 FLOOR MECHANICAL CLOSET ON BOTH SUPPY
 DUCTS.
  
 3.FIRE DAMPER ALSO REQUIRED AT 1ST
 FLOOR SUPPLY DUCT PENETRATING WALL AT
 THE ELEVATOR LOBBY.
  
 4.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATIONS.
  
 5.PLEASE NOTE, A MINIMUM OF 10 FT
 SEPARATION BETWEEN HOOD EXHAUST AND ANY
 FRESH AIR INTAKE, PROPERTY LINE OR
 ADJACENT BUILDINGS. NFPA 96 4-8.2.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.