Plan Review Notes
Plan Review Notes For Permit 03091147
Permit Number 03091147
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-10-02 00:00:001) PLEASE INDICATE EXISTING USE IF ANY
 FOR THE EXISTING BUILDING. IS THE
 BUILDING CURRENTLY OCCUPIED AND IF
 SO, SINGLE TENANT OR MULTIPLE TENANTS.
 IF BUILDING IS VACANT, HOW LONG HAS
 IT BEEN VACANT.
  
 2) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION ACTIVITIES TO COMPLY
 WITH NFPA 241.
  
 3) ALL DEBRIS IS TO BE REMOVED FROM
 THE BUILDING DAILY.
  
 4) STAIRS USED FOR EXITING IS TO BE
 PROVIDED.
  
 5) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY.
  
 6) PLEASE EXPLAIN RATIONALE FOR OPEN
 STAIR # 2.
  
 7) IT APPEARS THAT WINDOW OPENINGS MAY
 BE PRESENT NEAR EXIT ACCESS TO THE
 REAR STAIR.
  
 8) FUTURE KITCHEN MAKE-UP AND EXHAUST
 SHALL BE SEPARATED BY AT LEAST 10
 FEET.
  
 9) NOTE 14 ON PAGE A3.1 INDICATES 2
 HOUR FIRE SPRINKLER HEADS. PLEASE
 PROVIDE PRODUCT APPROVALS.
  
 10) PLEASE INDICATE EXIT DISCHARGE
 LOCATION FROM EXTERIOR STAIR. PLEASE
 DISPLAY 10 FEET HIGH, 10 FEET WIDE
 EXIT DISCHARGE. WHO'S PROPERTY DOES
 EXIT DISCHARGE OCCUR.
  
 11) PLEASE PROVIDE DETAILS ON
 EXTERIOR STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910