| 2003-10-02 00:00:00 | 1) PLEASE INDICATE EXISTING USE IF ANY |
| | FOR THE EXISTING BUILDING. IS THE |
| | BUILDING CURRENTLY OCCUPIED AND IF |
| | SO, SINGLE TENANT OR MULTIPLE TENANTS. |
| | IF BUILDING IS VACANT, HOW LONG HAS |
| | IT BEEN VACANT. |
| | |
| | 2) ALL DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION ACTIVITIES TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 3) ALL DEBRIS IS TO BE REMOVED FROM |
| | THE BUILDING DAILY. |
| | |
| | 4) STAIRS USED FOR EXITING IS TO BE |
| | PROVIDED. |
| | |
| | 5) ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST BE |
| | MARKED SHAFTWAY. |
| | |
| | 6) PLEASE EXPLAIN RATIONALE FOR OPEN |
| | STAIR # 2. |
| | |
| | 7) IT APPEARS THAT WINDOW OPENINGS MAY |
| | BE PRESENT NEAR EXIT ACCESS TO THE |
| | REAR STAIR. |
| | |
| | 8) FUTURE KITCHEN MAKE-UP AND EXHAUST |
| | SHALL BE SEPARATED BY AT LEAST 10 |
| | FEET. |
| | |
| | 9) NOTE 14 ON PAGE A3.1 INDICATES 2 |
| | HOUR FIRE SPRINKLER HEADS. PLEASE |
| | PROVIDE PRODUCT APPROVALS. |
| | |
| | 10) PLEASE INDICATE EXIT DISCHARGE |
| | LOCATION FROM EXTERIOR STAIR. PLEASE |
| | DISPLAY 10 FEET HIGH, 10 FEET WIDE |
| | EXIT DISCHARGE. WHO'S PROPERTY DOES |
| | EXIT DISCHARGE OCCUR. |
| | |
| | 11) PLEASE PROVIDE DETAILS ON |
| | EXTERIOR STAIR. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |