| Plan Review Notes For Permit 03091147 |
| Permit Number |
03091147 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-09 00:00:00 | *********UNSAT ******************* | | | | | | 1)NOTE: PLEASEE CLARIFY MEANS OF | | | LIGHTING CONTROLS FOR FIRST FLOOR, SHOWS | | | WHAT APPEARS TO NUMEROUS SWITCHES, BUT | | | FOR WHICH LTS? LS 101 5-8 | | | | | | 3)NOTE: PLEASESIZE GROUNDING ELOCTRODE | | | PER 250.66 | | | SHOWN AS#2?? | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PER 220 AND CONTINOUS LOADS PER 215.3/ | | | 230.42 ETC. | | | | | | 5)PLEASE SEE OTHER REVIEWERS COMMENTS | | | THAT MAY HAVE AN EFFECT ON ELECTRICAL | | | PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THER ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|