2003-10-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 13-103.1.1.1THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING AND PLUMBING SYSTEMS SHALL EACH
 SIGN THE ENERGY CODE COMPLIANCE FORM, TO
 CERTIFY COMPLIANCE.
  
 3) FBC 1010.3THE 1ST FLOOR ELEVATOR
 LOBBY IS IN FACT THE EXIT PASSAGEWAY
 FROM STAIR #1 TO THE EXIT DISCHARGE.
 THE EXIT PASSGEWAY SHALL NOT HAVE ANY
 OPENINGS OTHER THAN THE REQUIRED EXIT
 DOORS, SO THE ELEVATOR AND ELEVATOR
 MACHINE ROOM SHALL NOT BE ACCESSED FROM
 THIS SPACE.AMEND THE 1ST FLOOR PLAN.
  
 4) FBC 1006.2.5EXTERIOR STAIRWAY.
 AMEND THE PLANS TO CLARIFY WHERE THE
 EXTERIOR STAIRWAY DISCHARGES TO.
  
 5) FBC 1006.2.4THE EXTERIOR STAIRWAY/
 CATWALK PASSES A THIRD FLOOR WINDOW THAT
 DOES NOT HAVE A FIRE RESISTANCE RATING
 OF 1 HOUR.AMEND THE PLANS.IT IS
 NOTED THAT 2-HOUR RATED FIRE SPRINKLER
 HEADS (1 EXTERIOR AND 1 INTERIOR) HAVE
 BEEN SPECIFIED ABOVE EACH WINDOW.
  
 6) FBC 705.1.1.2SHEET A3.2, SOUTH
 ELEVATION.REPLACEMENT WINDOWS IN A
 WALL WITHIN 15 FEET OF THE PROPERTY LINE
 WILL REQUIRE OPENING PROTECTIVES.THIS
 APPLIES TO EXISTING BUILDINGS WHERE THE
 VALUE OF THE REPAIRS AND ALTERATIONS
 EXCEEDS 25% OF THE VALUE OF THE EXISTING
 BUILDING (REF FBC 3401,7,2,5).AMEND
 THE PLANS.IT IS NOTED THAT 2-HOUR
 RATED FIRE SPRINKLER HEADS (1 EXTERIOR
 AND 1 INTERIOR) HAVE BEEN SPECIFIED
 ABOVE EACH WINDOW.
  
 7) SHEET S-1, FOUNDATION PLAN STATES
 THAT NEW FOOTINGS ARE PROPORTIONED FOR
 2000 PSF ALLOWABLE BEARING PRESSURE.
 WHAT IS THE SIZE OF THE FOOTINGS FOR THE
 EXISING CONCRETE COLUMNS WHICH WILL
 RECEIVE INCREASED LOADING FROM THE
 NEW STAIR, SECOND FLOOR CONSTRUCTION AND
 ADDITIONAL ROOF MOUNTED EQUIPMENT.
  
 8) SHEET S-1, 2ND FLOOR FRAMING PLAN.
 NO BOTTOM REINFORCEMENT IS SHOWN IN THE
 SECOND SPAN OF THE NEW CONCRETE SLAB
 (EAST-WEST DIRECTION) ADJACENT THE NEW
 STAIRWAY.IS THIS INTENTIONAL?
  
 9) SHEET S-1, 2ND FLOOR FRAMING PLAN.
 AMEND THE PLANS TO CLARIFY THE SLAB
 FRAMING AROUND THE ELEVATOR SHAFT AND
 STAIRWELL.IS THE "PRE-ENGINEERED
 METAL PAN STAIR" SUPPORTED BY A CONCRETE
 LANDING SLAB AT 2ND FLOOR LEVEL, IF SO
 WHAT REINFORCEMENT IS SPECIFIED FOR THE
 LANDING SLAB?
  
 10) SHEET S-4STAIR SECTION.SUBMIT
 DETAILS FOR FORMING THE "NEW MONOLITHIC
 FOOTING" IN THE EXISTING SLAB AT THE
 BASE OF THE NEW STAIR.
  
 11) SHEET S-1PROVIDE AN ELEVATIONAL
 VIEW OF DETAIL 1/S-1 TO CLARIFY THE
 ARRANGEMENT OF THE 3/8" STIFFENERS, THE
 HILTI 1" DIA SUPER ROD AND THE 3/8" X 12
 AND 3/8" X 5" PLATES.
  
 12) SHEET S-5, CONCRETE NOTE #12 REFERS
 TO ACI 318-83 AND REINFORCING STEEL
 NOTE #9 REFERS TO ASTM A 185-68.
 FLORIDA BUILDING CODE 2001 (AS AMENDED)
 REFERS TO ACI 318-02 AND ASTM A 185-97
 RESPECTIVELY.AMEND THE NOTES.
  
 13) SUBMIT TWO COPIES OF A PRODUCT
 APPROVAL FOR THE NEW STOREFRONT, HOLLOW
 METAL DOORS, FIXED WINDOWS, SINGLE HUNG
 WINDOWS (AND SHUTTERS FOR ANY EXTERIOR
 GLAZING NOT SPECIFIED AS IMPACT RATED).
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.
  
 14) SHEET A2.3, ROOF PLAN.SUBMIT A
 PRODUCT APPROVAL FOR THE PROPOSED
 MODIFIED BITUMEN ROOFNG SYSTEM.
  
 15) FBC 11-4.1.3(11)ACCESSIBLE TOILET
 FACILITIES.AT THE TIME TENANT BUILD-
 OUT ACCESSIBLE TOILET FACILITIES WILL BE
 REQUIRED.
  
 16) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS