| 2003-10-21 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| | AND A COPY SUBMITTED TO THIS OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2) FBC 13-103.1.1.1THE PROFESSIONALS |
| | RESPONSIBLE FOR THE DESIGN OF THE |
| | BUILDING SHELL AND THE ELECTRICAL, |
| | LIGHTING AND PLUMBING SYSTEMS SHALL EACH |
| | SIGN THE ENERGY CODE COMPLIANCE FORM, TO |
| | CERTIFY COMPLIANCE. |
| | |
| | 3) FBC 1010.3THE 1ST FLOOR ELEVATOR |
| | LOBBY IS IN FACT THE EXIT PASSAGEWAY |
| | FROM STAIR #1 TO THE EXIT DISCHARGE. |
| | THE EXIT PASSGEWAY SHALL NOT HAVE ANY |
| | OPENINGS OTHER THAN THE REQUIRED EXIT |
| | DOORS, SO THE ELEVATOR AND ELEVATOR |
| | MACHINE ROOM SHALL NOT BE ACCESSED FROM |
| | THIS SPACE.AMEND THE 1ST FLOOR PLAN. |
| | |
| | 4) FBC 1006.2.5EXTERIOR STAIRWAY. |
| | AMEND THE PLANS TO CLARIFY WHERE THE |
| | EXTERIOR STAIRWAY DISCHARGES TO. |
| | |
| | 5) FBC 1006.2.4THE EXTERIOR STAIRWAY/ |
| | CATWALK PASSES A THIRD FLOOR WINDOW THAT |
| | DOES NOT HAVE A FIRE RESISTANCE RATING |
| | OF 1 HOUR.AMEND THE PLANS.IT IS |
| | NOTED THAT 2-HOUR RATED FIRE SPRINKLER |
| | HEADS (1 EXTERIOR AND 1 INTERIOR) HAVE |
| | BEEN SPECIFIED ABOVE EACH WINDOW. |
| | |
| | 6) FBC 705.1.1.2SHEET A3.2, SOUTH |
| | ELEVATION.REPLACEMENT WINDOWS IN A |
| | WALL WITHIN 15 FEET OF THE PROPERTY LINE |
| | WILL REQUIRE OPENING PROTECTIVES.THIS |
| | APPLIES TO EXISTING BUILDINGS WHERE THE |
| | VALUE OF THE REPAIRS AND ALTERATIONS |
| | EXCEEDS 25% OF THE VALUE OF THE EXISTING |
| | BUILDING (REF FBC 3401,7,2,5).AMEND |
| | THE PLANS.IT IS NOTED THAT 2-HOUR |
| | RATED FIRE SPRINKLER HEADS (1 EXTERIOR |
| | AND 1 INTERIOR) HAVE BEEN SPECIFIED |
| | ABOVE EACH WINDOW. |
| | |
| | 7) SHEET S-1, FOUNDATION PLAN STATES |
| | THAT NEW FOOTINGS ARE PROPORTIONED FOR |
| | 2000 PSF ALLOWABLE BEARING PRESSURE. |
| | WHAT IS THE SIZE OF THE FOOTINGS FOR THE |
| | EXISING CONCRETE COLUMNS WHICH WILL |
| | RECEIVE INCREASED LOADING FROM THE |
| | NEW STAIR, SECOND FLOOR CONSTRUCTION AND |
| | ADDITIONAL ROOF MOUNTED EQUIPMENT. |
| | |
| | 8) SHEET S-1, 2ND FLOOR FRAMING PLAN. |
| | NO BOTTOM REINFORCEMENT IS SHOWN IN THE |
| | SECOND SPAN OF THE NEW CONCRETE SLAB |
| | (EAST-WEST DIRECTION) ADJACENT THE NEW |
| | STAIRWAY.IS THIS INTENTIONAL? |
| | |
| | 9) SHEET S-1, 2ND FLOOR FRAMING PLAN. |
| | AMEND THE PLANS TO CLARIFY THE SLAB |
| | FRAMING AROUND THE ELEVATOR SHAFT AND |
| | STAIRWELL.IS THE "PRE-ENGINEERED |
| | METAL PAN STAIR" SUPPORTED BY A CONCRETE |
| | LANDING SLAB AT 2ND FLOOR LEVEL, IF SO |
| | WHAT REINFORCEMENT IS SPECIFIED FOR THE |
| | LANDING SLAB? |
| | |
| | 10) SHEET S-4STAIR SECTION.SUBMIT |
| | DETAILS FOR FORMING THE "NEW MONOLITHIC |
| | FOOTING" IN THE EXISTING SLAB AT THE |
| | BASE OF THE NEW STAIR. |
| | |
| | 11) SHEET S-1PROVIDE AN ELEVATIONAL |
| | VIEW OF DETAIL 1/S-1 TO CLARIFY THE |
| | ARRANGEMENT OF THE 3/8" STIFFENERS, THE |
| | HILTI 1" DIA SUPER ROD AND THE 3/8" X 12 |
| | AND 3/8" X 5" PLATES. |
| | |
| | 12) SHEET S-5, CONCRETE NOTE #12 REFERS |
| | TO ACI 318-83 AND REINFORCING STEEL |
| | NOTE #9 REFERS TO ASTM A 185-68. |
| | FLORIDA BUILDING CODE 2001 (AS AMENDED) |
| | REFERS TO ACI 318-02 AND ASTM A 185-97 |
| | RESPECTIVELY.AMEND THE NOTES. |
| | |
| | 13) SUBMIT TWO COPIES OF A PRODUCT |
| | APPROVAL FOR THE NEW STOREFRONT, HOLLOW |
| | METAL DOORS, FIXED WINDOWS, SINGLE HUNG |
| | WINDOWS (AND SHUTTERS FOR ANY EXTERIOR |
| | GLAZING NOT SPECIFIED AS IMPACT RATED). |
| | THE PRODUCT APPROVAL SHEETS SHALL BE |
| | MARKED, AS APPROPRIATE TO IDENTIFY WHICH |
| | PRODUCT OPTIONS/MATERIALS/SIZES ARE TO |
| | BE USED. |
| | |
| | 14) SHEET A2.3, ROOF PLAN.SUBMIT A |
| | PRODUCT APPROVAL FOR THE PROPOSED |
| | MODIFIED BITUMEN ROOFNG SYSTEM. |
| | |
| | 15) FBC 11-4.1.3(11)ACCESSIBLE TOILET |
| | FACILITIES.AT THE TIME TENANT BUILD- |
| | OUT ACCESSIBLE TOILET FACILITIES WILL BE |
| | REQUIRED. |
| | |
| | 16) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |