Plan Review Notes
Plan Review Notes For Permit 03091037
Permit Number 03091037
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-17 00:00:00************ PROVISO/ NOTES ************
  
 1)NOTE: PLEASE REVISE LOAD CALCUALTIONS
 AND SHOW ANY TRACK LIGHTING LOAD CALCS.
 PLEASE SEE 220.3,220.10,220.11,220.13
 AND 220.12B FOR TRK LTS.
 PLEASE SHOW ALL CONT LOADS PER 215.3,
 230.42
  
 2)NOTE: PLEASE SEE REDLINES ON PLANS
 AND SUBMIT A REVISED PLAN BEFORE FINAL.
 EGRESS LIGHTING REQD. LS 101 5-8
 ROOF TOP RECEPT FOR A/C EQUIPMENT 210.63
 CORRELATE ALL CIRCUITING ON PLANS WITH
 PANEL SCHEDULE(S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL. PLEASE NOTE THIS IS
 REQ'D BE ELECTRICAL CONTRACTOR.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ************* PROVISO ************
  
 1)NOTE: PLANS SHOW AN ADDITIONAL 100A
 PANEL IN STORAGE RM FOR ADJACENT TENANT
 SPACE. PLEASE SEE THAT THIS PANEL MUST
 BE ACCESSIBLE FROM OTHER TENANT SPACE.
 PANEL MAY BE MOVED OR REVERSED TO FACE
 INTO OTHER SPACE.(324) BANYAN
 FIRE RATING FOR TENANT SPACE 322MUST
 BE MAINTAINED.
  
 PLEASE NOTE: THIS MUST BE COMPLETED
 BEFORE C.O. CAN BE ISSUED ON SPACE 322.
  
 PLEASE HAVE AN ELECTRICAL CONTRACTOR
 SUBMIT FOR PERMIT TO MOVE PANEL OR?
 BEFORE C.O. 215.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW/ ELECTRICAL INSP.
 561-805-6717
 [email protected].