| 2003-09-17 00:00:00 | ************ PROVISO/ NOTES ************ |
| | |
| | 1)NOTE: PLEASE REVISE LOAD CALCUALTIONS |
| | AND SHOW ANY TRACK LIGHTING LOAD CALCS. |
| | PLEASE SEE 220.3,220.10,220.11,220.13 |
| | AND 220.12B FOR TRK LTS. |
| | PLEASE SHOW ALL CONT LOADS PER 215.3, |
| | 230.42 |
| | |
| | 2)NOTE: PLEASE SEE REDLINES ON PLANS |
| | AND SUBMIT A REVISED PLAN BEFORE FINAL. |
| | EGRESS LIGHTING REQD. LS 101 5-8 |
| | ROOF TOP RECEPT FOR A/C EQUIPMENT 210.63 |
| | CORRELATE ALL CIRCUITING ON PLANS WITH |
| | PANEL SCHEDULE(S). |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW BEFORE FINAL. PLEASE NOTE THIS IS |
| | REQ'D BE ELECTRICAL CONTRACTOR. |
| | IF THERE ARE ANY QUESTIONS,PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | ************* PROVISO ************ |
| | |
| | 1)NOTE: PLANS SHOW AN ADDITIONAL 100A |
| | PANEL IN STORAGE RM FOR ADJACENT TENANT |
| | SPACE. PLEASE SEE THAT THIS PANEL MUST |
| | BE ACCESSIBLE FROM OTHER TENANT SPACE. |
| | PANEL MAY BE MOVED OR REVERSED TO FACE |
| | INTO OTHER SPACE.(324) BANYAN |
| | FIRE RATING FOR TENANT SPACE 322MUST |
| | BE MAINTAINED. |
| | |
| | PLEASE NOTE: THIS MUST BE COMPLETED |
| | BEFORE C.O. CAN BE ISSUED ON SPACE 322. |
| | |
| | PLEASE HAVE AN ELECTRICAL CONTRACTOR |
| | SUBMIT FOR PERMIT TO MOVE PANEL OR? |
| | BEFORE C.O. 215.5 |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW/ ELECTRICAL INSP. |
| | 561-805-6717 |
| | [email protected]. |