| Plan Review Notes For Permit 03091015 |
| Permit Number |
03091015 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-15 00:00:00 | | | | FAILED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THE 4/0 FEEDERS FROM THE 600 AMP TRIP | | | BREAKER ARE TOO SMALL FOR THE OCP PER | | | 310.16 NEC.CORRECT OCP OR WIRE SIZE AND | | | RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|