2004-01-15 00:00:00 
 FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE 4/0 FEEDERS FROM THE 600 AMP TRIP
 BREAKER ARE TOO SMALL FOR THE OCP PER
 310.16 NEC.CORRECT OCP OR WIRE SIZE AND
 RESUBMIT FOR REVIEW.
  