Plan Review Notes For Permit 03091015
Permit Number 03091015
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-22 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE PLANS FOR REVIEW
 INDICATING PROPER PRIMARY & SECONDERY
 OVERCURRENT PROTECTION PER 450.3(B).
  
 NOTE: PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.THE NUMER OF
 THE ENGINEER OR ENGINEERING BUSINESS IS
 A REQUIREMENT OF THIS ARTICLE.
 ALSO A SIGNATURE IS A REQUIREMENT OF
 471.025,NOT INITIALS.
  
 ALSO VERIFY SIZE AND NUMBER OF CONDUCTOR
 IN THE PRIMARY AND SECONDARY.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.