| Plan Review Notes For Permit 03090979 |
| Permit Number |
03090979 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-07-27 00:00:00 | ** REDLINED ** | | | | | | CONDUCTORS FROM GUTTER TO PANEL "T" TO | | | BE SIZED PER 310.16 (75) DEGREE COL. | | | 350MCM AS SHOWN IS NOT LARGE ENOUGH. |
|