| Plan Review Notes For Permit 03090979 |
| Permit Number |
03090979 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | | | | 1) PER CALCULATIONS PROVIDED IN RESPONSE | | | TO 1ST REVIEW, MORE FIXTURES WILL BE RE- | | | QUIRED PER TABLE 403. WITH THE CHURCH | | | OCCUPANCY BEING 2958 DEVIDED BY 7 NET = | | | 422.57 ROUNDED UP TO 423 DIVIDED BY 2 = | | | 111.5 ROUNDED UP TO 112. PER POTTY PARI- | | | TY THAT IS 2 FOR MEN & 3 FOR WOMEN. THE | | | BUSINESS AREA IS 2824 DIVIDED BY 100 = | | | 28.24 ROUNDED UP TO 29 IS ONE WATER | | | CLOSET AND STORAGE IS 965 DIVIDED BY | | | 300 (TABLE 1003.1) = 3.21 ROUNDED UP TO | | | 4. ADDED TO THE 29 FROM BUSINESS THERE | | | WILL STILL BE ONE MORE WATER CLOSET REQ- | | | UIRED MINIMUM. IF ADDED TO THE MENS | | | TOILET ROOM THEN POTTY PARITY IS NOT | | | BEING ADDRESSED. | | | 2) SHT ME2 HAS NOT CHANGED. INFORMATION | | | HAS BEEN TRANSFERRED TO SHT ME1 AND ME2 | | | STILL HAS INCORRECT WATER RISER. A NEW | | | SHEET SP-1 HAS BEEN ADDED FOR INFORMAT- | | | ION PREVIOUSLY ON SHT ME1. PLEASE | | | CLAIRFY, AS THE INFORMATION CAN NOT BE | | | APPROVED. | | | 3) ENGINEERS NAME AND LICENSE NUMBER | | | MISSING FROM SHTS ME2 AND SP-1. | | | 61G15-23.002(2) & FS 471 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|