| Plan Review Notes For Permit 03090897 |
| Permit Number |
03090897 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2003-12-22 00:00:00 | REVISION DENIED | | | | | | 1) SUBMIT REVISED FOUNDATION, ROOF | | | FRAMING PLANS AND ELEVATIONS FOR GUEST | | | HOUSE. TIE TO BEAM, COLUMN, FOOTER, | | | TRUSS ANCHOR, WINDLOAD SCHEDULES ON THE | | | APPROVED PLANS OR SUBMIT NEW SCHEDULES. | | | | | | 2) THE DRAWINGS FROM THE ARCHITECT ARE | | | REQUIRED TO BE SIGNED, SEALED AND DATED. | | | THE DRAWING THAT WAS SUBMITTED HAS | | | COPIED SIGNATURES. THE ORIGINAL WET | | | SIGNATURE OF THE ARCHITECT IS REQUIRED. | | | | | | 3) SUBMIT PRODUCT APPROVAL FOR THE | | | MULLION THAT IS BETWEEN THE FRENCH DOOR | | | WITH SIDELITES AND THE FIXED GLASS ARCH | | | TRANSOM. THE PRODUCT APPROVAL SUBMITTED | | | WILL IS NOT ACCEPTABLE AT THIS LOCATION. | | | IF THE STEEL HEADER DETAIL ON A9 IS TO | | | BE USED, INDICATE THIS ON DRAWING. | | | | | | 4) SUBMIT PRODUCT APPROVAL FOR THE F.G. | | | ARCHED WINDOW ABOVE THE FRENCH DOOR W/ | | | SIDELITES. | | | | | | 5) MAKE THE PLUMBING AND MECHANICAL | | | CORRECTIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|