| 2003-11-04 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING CORRECTIONS | | | FROM THE PREVIOUS REVIEWS HAVE NOT BEEN | | | CORRECTED. | | | | | | 1} THE EQUIPMENT GROUNDS BEING RAN WITH | | | THE FEEDERS FROM THE METER TO THE FIRST | | | MEANS OF DISCONNECT CREATE A PARALLEL | | | RETURN PATH WITH THE NEUTRAL AND MUST | | | NOT BE INSTALLED PER 250.6(B). | | | | | | 2} THE FEEDER TO PANEL "C" IS MISMARKED | | | ON THE RISER DIAGRAM. NOTE THEY ARE | | | MARKED AS 3-#8/0,AND 1-#2 EQ.GND IN A | | | 1" CONDUIT.PLEASE CORRECT TO REFLECT THE | | | SIZE ACTUALLY INTENDED TO BE INSTALLED. | | | | | | 3} IN PANEL "B" THE FEEDER FOR PANEL "C" | | | IS SHOWN AS A #8, BUT HAS AN | | | OVERCURRENT DEVICE FOR A #6. ALSO A #8 | | | IS NOT RATED FOR MORE THAN A 55 AMP | | | LOAD,NOTE THAT THE DEMAND ON PANEL "C" | | | IS 58.3 AMPS.SEE 310.16. | | | | | | IF THERE ARE ANY QUESTIONS OR IF THE | | | ARCHITECT WOULD LIKE TO MEET REGARDING | | | ANY OF THESE COMMENTS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|