Plan Review Notes
Plan Review Notes For Permit 03090897
Permit Number 03090897
Review Stop E
Sequence Number 3
Notes
Date Text
2003-11-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING CORRECTIONS
 FROM THE PREVIOUS REVIEWS HAVE NOT BEEN
 CORRECTED.
  
 1} THE EQUIPMENT GROUNDS BEING RAN WITH
 THE FEEDERS FROM THE METER TO THE FIRST
 MEANS OF DISCONNECT CREATE A PARALLEL
 RETURN PATH WITH THE NEUTRAL AND MUST
 NOT BE INSTALLED PER 250.6(B).
  
 2} THE FEEDER TO PANEL "C" IS MISMARKED
 ON THE RISER DIAGRAM. NOTE THEY ARE
 MARKED AS 3-#8/0,AND 1-#2 EQ.GND IN A
 1" CONDUIT.PLEASE CORRECT TO REFLECT THE
 SIZE ACTUALLY INTENDED TO BE INSTALLED.
  
 3} IN PANEL "B" THE FEEDER FOR PANEL "C"
 IS SHOWN AS A #8, BUT HAS AN
 OVERCURRENT DEVICE FOR A #6. ALSO A #8
 IS NOT RATED FOR MORE THAN A 55 AMP
 LOAD,NOTE THAT THE DEMAND ON PANEL "C"
 IS 58.3 AMPS.SEE 310.16.
  
 IF THERE ARE ANY QUESTIONS OR IF THE
 ARCHITECT WOULD LIKE TO MEET REGARDING
 ANY OF THESE COMMENTS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718