Plan Review Notes
Plan Review Notes For Permit 03090897
Permit Number 03090897
Review Stop P
Sequence Number 2
Notes
Date Text
2003-12-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A. SHOWER IN CABANA BATH IS NOT VENTED.
 901.2.1
 B. NO VEG SINK SHOWN ON RISER. 104.2.1
 C. BIDET NOT VENTED, AND A TRAP IS RE
 QUIRED. 901.2.1 - 1002.1
 D. WASH MACHINE AND LAUNDRY SINK ARE ON
 DIFFERENT WALLS. EITHER SEPARATE STACKS
 ARE REQUIRED OR SHOW WASTE ARM TO SINK
 ON RISER. 104.2.1 - A CLEANOUT IS REQ-
 UIRED AT 4' ABOVE THE FLOOR ON THE WASH
 MACHINE STACK. 708.10 - WASH MACHINE AND
 LAUNDRY SINK SHALL NOT CONNECT TO THE
 STACK ON A DOUBLE SANITARY TEE (CROSS)
 706.3.
 E. STUDIO BATH RISER AND FLOOR PLAN DO
 NOT REFLECT EACH OTHER. (SHOWER NOT TUB)
 F. SEE RED LINE CORRECTIONS ON SANITARY
 RISER DIAGRAM AND MAKE ADJUSTMENTS FOR
 RESUBMITING REVISION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]