| Plan Review Notes For Permit 03090897 |
| Permit Number |
03090897 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-12-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS, NOR DOES IT REFLECT | | | THE FLOOR PLAN. | | | A. SHOWER IN CABANA BATH IS NOT VENTED. | | | 901.2.1 | | | B. NO VEG SINK SHOWN ON RISER. 104.2.1 | | | C. BIDET NOT VENTED, AND A TRAP IS RE | | | QUIRED. 901.2.1 - 1002.1 | | | D. WASH MACHINE AND LAUNDRY SINK ARE ON | | | DIFFERENT WALLS. EITHER SEPARATE STACKS | | | ARE REQUIRED OR SHOW WASTE ARM TO SINK | | | ON RISER. 104.2.1 - A CLEANOUT IS REQ- | | | UIRED AT 4' ABOVE THE FLOOR ON THE WASH | | | MACHINE STACK. 708.10 - WASH MACHINE AND | | | LAUNDRY SINK SHALL NOT CONNECT TO THE | | | STACK ON A DOUBLE SANITARY TEE (CROSS) | | | 706.3. | | | E. STUDIO BATH RISER AND FLOOR PLAN DO | | | NOT REFLECT EACH OTHER. (SHOWER NOT TUB) | | | F. SEE RED LINE CORRECTIONS ON SANITARY | | | RISER DIAGRAM AND MAKE ADJUSTMENTS FOR | | | RESUBMITING REVISION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|